Analysis of the Failure of a 750 kV Tank Type SF₆ Compressed Gas Circuit Breaker
Failure PhenomenonFailure Information and Operational Mode Before FailureAt 17:53:50 on May 16, 2016, the protection devices of two sets on Jingchuan II Line operated successively. Phase B was selected for tripping, and the B - phase of circuit breakers 7522 and 7520 was opened. The protection of circuit breaker 7522 detected a permanent fault on the two - circuit line protection device, with a delay of 0.6s. Subsequently, the ABC three - phase of circuit breaker 7522 tripped. During this proces