Combined with the fault recording waveform of the CSL103 protection device, after the B - phase of the 7522 circuit breaker was re - closed, the protection issued a three - phase tripping command at 767 ms, and the three phases of the 7522 circuit breaker were fully opened at 825 ms, with an action time of 58 ms. During the arc - extinguishing process of the B - phase circuit breaker, the current waveform did not cross zero, and the arc continued to provide short - circuit current inside the circuit breaker.
According to the arc - extinguishing performance analysis of SF₆ gas: under the action of the arc, SF₆ gas absorbs electrical energy and generates low - fluorine compounds. However, when the arc current crosses zero, the low - fluorine compounds can quickly recombine into SF₆ gas. The dielectric strength of the arc gap recovers relatively quickly. Since the arc current did not cross zero, the arc - extinguishing performance of SF₆ gas decreased. At this time, only by activating the circuit breaker failure protection could the adjacent 7512 circuit breaker cut off the fault current. The time from the three - phase tripping position contact of the 7522 circuit breaker returning to the three - phase tripping position contact of the 7512 circuit breaker returning was 317 ms in total, indicating that the high - energy arc of the B - phase circuit breaker burned for 317 ms. After the 7512 circuit breaker opened, the arc was extinguished.
In conclusion, the line protection and circuit breaker failure protection in this event both operated normally, and the circuit breaker tripped normally. The actions of primary and secondary equipment were all correct. For the B - phase of the 7522 circuit breaker, from the gas composition analysis, there was high - intensity energy in the arc - extinguishing chamber, which was sufficient to increase the gas pressure. However, the current of the 7522B phase did not cross zero, and the arc was not extinguished. But the valve of the lower compression chamber had been opened, and the excess gas was discharged from the lower part, which might carry the arc out and burn out the insulating tie - rod of the moving contact and the shunt capacitor.
Analysis of the Causes of the Burn - out of the Circuit Breaker Closing Resistance and the Breakdown of the Uniform Shielding Cover on the Outer Side of the Resistance
The operation of the circuit breaker is the cause of most switching over - voltages. Installing a closing resistance can effectively limit the over - voltages during line closing and single - phase reclosing. The 550/800PMSF₆ gas - blast circuit breaker manufactured by ABB Company used in our company has a closing resistance composed of stacked silicon carbide resistance plates. According to the manufacturer's instruction manual, the heat capacity of the closing resistance is as follows: when closing 4 times at 1.3 times the rated phase voltage, the time interval between the first two times is 3 minutes, and the time interval between the last two times is 3 minutes; the time interval between the two groups of tests (front and back) does not exceed 30 minutes.
The breaker has a series - type break structure, which consists of 3 main breaks, 1 auxiliary break, and a combined closing resistance, as shown in Figure 2. The main feature of the series - type break is that during the closing operation of the circuit breaker, the auxiliary break closes after the main break in the arc - extinguishing chamber, and during the opening operation, the auxiliary break also separates after the main break in the arc - extinguishing chamber.
That is, the action sequence of the auxiliary break is closing later and opening later. Its working principle is as follows: during closing, the main break closes first, forming a current - conducting loop in series with the resistance, and the closing resistance is connected. After about 8 - 11 ms (according to the manufacturer's instruction manual), a current - conducting loop is formed through the closing contact of the auxiliary break, short - circuiting the closing resistance; during opening, the main break disengages first, opening the main current loop, and then the auxiliary break separates.
Therefore, the auxiliary break carries the rated current and the short - circuit current during opening. After the B - phase mechanical opening, the closing resistance is connected to the circuit. Since the arc between the B - phase breaks lasted for 317 ms through the closing resistance, and the arc current was approximately 1620 A, according to the calculation, the heat capacity borne by the closing resistance was greater than its rated capacity. This led to the over - limit heat capacity of the connection ring between the closing resistance and the auxiliary break, eventually causing fusing, discharging to the outer - wall grading ring, resulting in the breakdown of the grading ring and the blackening of the resistance.

Analysis of the Causes for the Operation of Circuit Breaker Failure Protection
In circuit breaker failure protection, when the current element is activated and meets the failure protection criteria, the failure protection will be initiated as long as the protection trip input is received and the corresponding phase current is greater than 0.05 In.
As can be seen from the reports of 7522, from 775 ms when the PRS - 721S protection device of the 7522 circuit breaker protection panel received the three - phase trip signal input from the IRC - 931BM protection device of the Jingchuan II line protection, to 925 ms when it tripped the local circuit breaker due to failure, and to 1025 ms when it tripped the adjacent circuit breaker due to failure, with a delay of 0.15 s for tripping the local circuit breaker and 0.25 s for tripping the adjacent circuit breaker respectively, which is in line with the operation logic of failure protection, and the protection operated correctly, as shown in Figure 3. In the oscillogram, it can be seen that although the B - phase tripping position contact of 7522 had returned at 825 ms, there was still current (arc) flowing between the moving and stationary contacts.

Conclusions
- Due to the severe distortion of the fault current, the waveform shifted to the lower side of the time - axis. The fact that the waveform did not cross zero within the effective arc - extinguishing time of the circuit breaker was the main reason for the non - extinction of the arc. The failure of the gap insulation to recover after the circuit breaker opened and the decline in the arc - extinguishing performance of SF₆ gas were secondary reasons for the non - extinction of the arc.
- The non - extinction of the arc and the expulsion of the remaining gas from the arc - extinguishing chamber, which carried out the arc, were the main reasons for the blackening of the insulating tie - rod and the outer wall of the capacitor.
- After the mechanical opening of phase B, the closing resistance was connected to the circuit. Since the arc between the breaks of phase B flowed through the closing resistance for 317 ms, the heat capacity caused the heat capacity of the connection between the closing resistance and the auxiliary break to break down, eventually leading to fusing, discharging to the outer - wall grading ring, resulting in the breakdown of the grading ring and the blackening of the resistance.
- The presence of arc current in phase B and its compliance with the operation logic of the circuit breaker failure protection were the main reasons for the tripping of the busbar.