Hybrid Circuit Breaker with IGBT Simulink Electronic Interruption
In a hybrid circuit breaker with IGBT Simulink electronic interruption (as shown in the left figure), the fault current is diverted from the main path to the interrupter path by the IGBTs in path 1. Meanwhile, a local current zero-crossing is created by a set of IGBTs in path 2.
In the right figure, the short-circuit fault current begins to flow through the circuit breaker at t1. Then, at t2 , the current is interrupted in path 1 (as shown in the left figure), and the fault current is diverted to path 2. Next, at t3 , the current is interrupted in path 2 and diverted to path 3. The high impedance of path 3 causes a sharp rise in voltage until the surge protector limits this voltage at t4. This voltage is known as the Transient Interruption Voltage (TIV).
It is important to recognize that from t4 onward, the system begins to recover, even though the current at the fault location has not yet been completely interrupted. The faulty section is effectively isolated from the normal part of the system. From this point, the voltage (higher than the rated system voltage) steadily reduces the current to zero, while the system's inductive energy dissipates in the surge protector in path 4.
Diagram Explanation
System Recovery Process
By this method, the hybrid circuit breaker can quickly and effectively handle short-circuit faults, protecting the power system from damage.