Brand | Wone |
Model NO. | WDQT-203 gas relay calibration |
Rated voltage | 220V |
Series | WDQT-203 |
Description
Gas relay calibration is a special equipment for the flow speed and volume value of gas relay for power transformer.
The detector adopts advanced microcontrol technology to calculate the flow speed by the instantaneous burst pulse pressure method of the transformer to detect the high precision pressure sensor and micropressure sensor.
Specifications
Flow speed detection
Flow speed detection | 0.5~1.6m/s |
display resolution | 0.01m/s |
precision | 1.0 level |
the error of | ≤ 0.04m/s |
Capacity detection
Capacity detection | 0~400ml |
display resolution | 0.1 ml |
precision | 1.0 level |
the error | ≤ 5% |
Seal detection
Seal detection | 0~150KPa |
display resolution | 0.1KPa |
precision | level 1.0 |
detection time | 0~60min optional |
Test medium | 25 # transformer oil |
Execution standard: DL/T540-94[Gas Relay Inspection Specification] Gas relay flow rate, capacity and seal detection.