• Counter For Surge Arrester for recording the operation times
  • Counter For Surge Arrester for recording the operation times
Counter For Surge Arrester for recording the operation times
discuss personally
Model
JSY-11S
Basic info
Brand Wone
Model NO. Counter For Surge Arrester for recording the operation times
Nominal Discharge Current 10kA
Residual Voltage not Exceeds 2kA
Series Arrester Auxiliary Equipment
Product Detail

Description:

JSY-11S surge arester counter is a device for recording the operation times of a lightning arrester under the lightning arrester connecting in series. It is applicable to lightning arrester with grade not exceeding 220KV. The environmental condition of using site is the same to the connecting lightning arresters. It is not applicable to places with heavy pollution and strenuous vibration. It applies zinc oxide varistor and has relative improvement on the electrical performance.

Using conditions:

  • It is applicable to exterior or interior.

  • Environmental temperature (-40 to +40) C . 

  • The altitude can't be over 2000m.

  • Supply frequency (48 to 62) Hz.

  • No place with strenuous vibration.

Structure and characteristic:

Electric Principle:

  • A discharge counter mainly consists of components like sampling varistor, silicon bridge rectifier, high-voltage condenser and electromagnetic counter, etc. The discharge current of lightning arrester generates voltage on the varistor (nonlinear resistance), and charges on condenser through silicon bridge rectifier and discharge to electromagnetic counter. The counter records every time it discharges, so as to realize the operation times of lightning arrester.

  •  The enclosure of this product applies premium stainless steel enclosure. It has good rot resistance and good sealing property, not being influenced by external environment. Inner components have good ageing resistance, which can run in the electric power system for long term.

JSY-11S lightning arrester discharge counter applies dual pointer display. The display has the advantages like clear display and easy observation, etc. The counting cycle index is from 0 to 999, which is to say 1000 times for a cycle. It is beneficial to record the times of lightning of going through the lightning arrester relatively completely in a short time.

Main Technical Properties:

Product implementing standard: JB/T 10492-2011 Monitoring Device for Metal Oxide Lightning Arrester. The main technical properties are as the below table:

image.png

Inspection and acceptance & installation:

 Inspection and Acceptance:

  •  When inspect and accept products, open the packing case and inspect whether the accompanying documents (operation manual,packing list and certificate of approval) are complete.

  •  Inspect whether the accessories are complete according to the packing list. Meanwhile, inspect whether the product appearance has scrape and whether the insulator has crack and dropped piece.

When installing, the dig angle between the plane of the panel of counter and the horizontal plane should be smaller than 85° , so as to avoid waterlogging influencing observation. Use M10 bolts to fix the metal enclosure base to the metal support and connect the ground through the ground bus. (The monitor base can also be the ground bus.) Another end connects the electrode through the top of the insulator and connects the low-pressure end of the lightning arrester by wire (or aluminum strip). It must install securely and contact reliably.(Installation dimension please see the attached drawing.)

Test methods:

When users receive products, they can use the below methods to test the products.

  • Operation Performance Test: Connect a condenser with withstand voltage over 500V and capacity over 5MFD to a 500V megger. Rotate the megger with the rotate speed of 90 to 120 per minute to charge the condenser. When the voltage of the condenser is monitored to be 300V by universal meter, disconnect the condenser connecting with the megger. Use the condenser to discharge the counter instantaneously and the discharge counter should count it as once. Perform it for 10 times consecutively and they should be reliable operations.

  • The test of discharge counter can also be performed by the specialized tester produced by our factory. For details please see Instruction of JCQT6000 Lightning Arrester Monitor Tester.

Precautions:

  • After putting the discharge counter into operation, operators on duty shall keep monitoring it and record the reading of the discharge counter regularly, so as to master the times of lightning current going through the lightning arrest.

  • Note to not overstress on the insulator to avoid destroying the sealing. Meanwhile, users can not take apart the lightning arrester discharge counter casually.

Quality assurance:

On the condition of user using and installing the product according to regulations, the company is responsible for the “Three Guarantees” after-sales service within the period of “Three Guarantees” . The period of “Three Guarantees” is a year. If user has special requirements, he can come and mail for negotiation.

image.png

Schematic Diagram of Structure and Installation

How does a surge arrester counter work?

When a surge current (such as overcurrent caused by lightning) passes through the surge arrester, the arrester operates to divert the surge current into the ground. At the same time, the current sensor in the connected surge arrester counter detects this current signal. The signal generated by the sensor is then converted and processed by the signal processing circuit. After processing, the signal triggers the counting unit to increment the count, causing the displayed number to increase by one, indicating that the arrester has performed one operation.

Know your supplier
Wone
Main Categories
High voltage/Low voltage/Wire cable/Instrument meters/New energy/Tester/Production equipment/Generator/Electrical fittings/Integrated Electrical Equipment
Business Type
Design/Manufacture/Sales
Highest Annual Export (USD)
$50,000,000
Professional Experience
1 years
Workplace
65666m²m²
占位
占位
Related Products
Related Knowledges
Failure Analysis and Design Optimization of Conventional Grounding Transformers
Failure Analysis and Design Optimization of Conventional Grounding Transformers
I. Core Cause of Damage: Electrodynamic Impact (Complying with GB/T 1094.5 / IEC 60076-5)The direct cause of high-voltage winding end collapse is the instantaneous electrodynamic impact induced by short-circuit current. When a single-phase grounding fault occurs in the system (such as lightning overvoltage, insulation breakdown, etc.), the grounding transformer, as the fault current path, withstands high-amplitude and steep-rise-rate short-circuit currents. According to Ampère's force law
Felix Spark
06/12/2025
Analysis of Grounding Transformer Operational Behavior Under System Single-Phase-to-Ground Fault Conditions
Analysis of Grounding Transformer Operational Behavior Under System Single-Phase-to-Ground Fault Conditions
1 Theoretical AnalysisIn distribution networks, grounding transformers serve two key roles: powering low - voltage loads and connecting arc - suppression coils at neutrals for grounding protection. Grounding faults, the most common distribution network fault, heavily impact transformers’ operating characteristics, causing sharp changes in electromagnetic parameters and status.To study transformers’ dynamic behaviors under single - phase grounding faults, build this model: Assume a tr
Felix Spark
06/12/2025
Design Calculations for Neutral Grounding Schemes and Grounding Transformer Sizing in Utility-Scale Solar PV Plants
Design Calculations for Neutral Grounding Schemes and Grounding Transformer Sizing in Utility-Scale Solar PV Plants
1 Classification of Neutral Grounding Methods for Solar Photovoltaic Power StationsInfluenced by differences in voltage levels and grid structures across regions, the neutral grounding methods of power systems are mainly categorized into non-effective grounding and effective grounding. Non-effective grounding includes neutral grounding via arc suppression coils and neutral ungrounded systems, while effective grounding comprises neutral solid grounding and neutral grounding via resistors. The sel
Dyson
06/12/2025
Zero-Sequence Impedance Characterization of Dry-Type Grounding Transformer with ZN Connection
Zero-Sequence Impedance Characterization of Dry-Type Grounding Transformer with ZN Connection
In a neutral-insulated three-phase power system, an earthing transformer provides an artificial neutral point, which can be solidly earthed or earthed via reactors/arc suppression coils. The ZNyn11 connection is typical, where zero-sequence magnetomotive forces in the inner/outer half-windings of the same core column cancel out, balancing fault currents in series windings and minimizing zero-sequence leakage flux/impedance.Zero-sequence impedance is critical: it determines fault current magnitud
Dyson
06/12/2025
Case Analysis on Maloperation of Grounding Transformer Overcurrent Protection Relay
Case Analysis on Maloperation of Grounding Transformer Overcurrent Protection Relay
The neutral grounding mode refers to the connection between the power system neutral point and ground. In China's 35 kV and below systems, common methods include ungrounded neutral, arc-suppression coil grounding, and small-resistance grounding. The ungrounded mode is widely used as it allows short-term operation during single-phase grounding faults, while small-resistance grounding has become mainstream for its fast fault removal and overvoltage limitation. Many substations install grounding tr
Felix Spark
06/12/2025
Discussion on the Design of Low Zero-Sequence Impedance Grounding Transformers
Discussion on the Design of Low Zero-Sequence Impedance Grounding Transformers
With the expansion of power system scale and the cableization process of urban power grids, the capacitive current in 6kV/10kV/35kV power grids has significantly increased (generally exceeding 10A). As power grids at this voltage level mostly adopt neutral ungrounded operation mode, and the distribution voltage side of main transformers is usually in delta connection, lacking a natural grounding point, the arc during ground faults cannot be reliably extinguished, necessitating the introduction o
Dyson
06/11/2025
×
Inquiry
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!
商品视频播放