Brand | ROCKWILL |
Model NO. | RCW S15.6M MV outdoor vacuum recloser |
Rated voltage | 15.6kV |
Rated normal current | 1250A |
Rated short circuit breaking current | 25kA |
Power frequency withstand voltage | 60kV/min |
Rated lightning impulse voltage | 125kV |
manual closing | Yes |
Series | RCW |
Description:
The RCW series automatic circuit reclosers can use on overhead distribution lines as well as distribution substation applications for allvoltage classes 11kV up to 38kV at 50/60Hz power system. and it’s rated current can reach 1250A.The RCW series automatic circuit reclosers integrates the functions of control, protection, measurement, communication, fault detection, on-line monitoring of closing or opening.The RCW series vacuum recloser is mainly combined with integration terminal, current transformer, permanent magnetic actuator and it’s recloser controller.
Features:
Optional grades available in rated current range.
With optional relay protection and logic for user selection.
With optional communication protocols and I/O ports for users to choose.
PC software for controller testing, setup, programming, updates.
Parameters:
Rated maximum voltage |
15.6kV |
|
Rated maximum current |
1250A |
|
Rated frequency |
50Hz |
|
Rated short circuit breaking current |
12.5kA |
|
Rated peak value withstand current |
31.5kA |
|
Rated 1min power frequencywithstand voltage(Single-phase Silicone rubber pole (unable the gas)) |
60kV |
|
Rated lightning impulse voltage(Single-phase Silicone rubber pole (unable the gas)) |
125kV |
|
Operation sequence |
C-0.5-CO-2-CO-5-CO(Magnetic actuator) |
|
Mechanical life |
n:30000(Magnetic actuator) |
|
Power supply and operating voltage |
110/220V( Customized) |
|
Ratio of current transformer |
400/1A( Customized) |
|
Number of voltage sensors(Single-phase Silicone rubber pole (unable the gas)) |
≤1 |
|
Opening time |
≤20ms(Magnetic actuator) |
|
Closing time |
≤30ms(Magnetic actuator) |
|
Minimum creepage distance |
31,level4(mm/kv) |
|
Minimum distance between phases |
360mm |
|
Potential transformer |
110/220V( Customized) |
|
Cable length |
6,8,12m( Customized) |
|
Cable clamp(Single-phase Silicone rubber pole (unable the gas)) |
2-hole NEMA |
|
Lightning arrester |
≤6 |
|
Mounting type |
Single / double column |
With optional relay protection& logics for user choice |
Instantaneous over-current protection |
|
Timing over-current protection |
||
Negative sequence over-current protection |
||
Directional over-current protection(*) |
||
Over-voltage protection./Under voltage protection |
||
Programable protection relay curves total 10 nos ANSI/IEC curves |
||
Cold load pickup protection TCC +Hot line tag |
||
Earth protection EF/SEF +Zone Sequence Co-ordination |
||
More relay functions can be customized |
||
With optional communication protocols & I/O port for user choice |
RS-232 and RS-485 ports supporting |
|
DNP3.0 communication protocol support(*) |
||
Modbus communication protocol is optional(*) |
||
IEC 60870-5-101 communication protocol support |
||
IEC 60870-5-104 communication protocol support.(*) |
||
The recloser can communicate through GPRS(Or GSM) modem with English or Specified language (*) |
||
With optional functions for use |
Rated currents, System phase current. |
|
Rated voltages, System phase voltage& secondary low voltage power supply voltage. Frequency, power(kWh), reactive power(kV arh), power factor |
||
With optional reclosing interval for user pre-program |
Reclosing times setting support |
|
Dead time setting support |
||
With events recording function |
SOE 10000 operations record |
|
Fault record and normal operation record |
||
Note: (*) mean should customized by manufacturer if needed |
External dimensions:
Environmental requirement:
Maximum temperature: |
+40℃ |
Minimum temperature: |
-30℃ |
Monthly average humidity |
95% |
Humidity: |
90% |
Above sea level: |
2500m or higher |
Ambient air not apparently polluted by corrosive and flammable gas, vapor |
Product show:
What are the technical parameters of the outdoor vacuum recloser?
Rated Voltage: 38kV, indicating the voltage level at which the recloser can operate normally. This ensures that the insulation and electrical performance of the device meet the required standards at this voltage.
Rated Current: Available in various specifications, such as 800A, 1200A, etc. This represents the maximum current that the recloser can carry continuously during normal operation. The appropriate rated current value should be selected based on the load current of the line.
Rated Short-Circuit Breaking Current: Reflects the breaking capability of the recloser during short-circuit faults. Common specifications include 16kA, 20kA, etc. A higher short-circuit breaking current indicates that the recloser can more reliably interrupt short-circuit currents, protecting the safety of the power system.
Rated Short-Circuit Making Current: Represents the maximum peak current that the recloser can close during a short-circuit fault. This value is typically greater than the rated short-circuit breaking current to ensure that the recloser can reliably close and withstand the impact of short-circuit currents at the moment of fault.
Reclosing Time Interval: Generally adjustable between 0.5 seconds and several seconds. Depending on the requirements of different power systems and types of faults, an appropriate reclosing time interval can be set to enhance the reliability and continuity of power supply.