• High - voltage pneumatic load break switch
High - voltage pneumatic load break switch
discuss personally
Model
FKN-12/630
Basic info
Brand ROCKWILL
Model NO. High - voltage pneumatic load break switch
Rated voltage 12kV
Rated normal current 630A
Rated frequency 50/60Hz
Series FKN
Product Detail

Product Overview

The s high - voltage pneumatic load break switches and their combined electrical appliances are indoor high - voltage switchgear for AC 12kV, 50Hz. This load break switch features high specific technical parameters and reliable action. The basic form of the operating mechanism is manual spring - energy - storage type, and it can also be equipped with an electromagnetic spring operating mechanism. Based on the pneumatic arc - extinguishing principle, it can interrupt multiple times without replacing the arc - extinguishing tube.

The high - voltage load break switch can close, carry and open load currents under normal circuit conditions, and has the capability to close short - circuit currents and open short - circuit currents within a specified short time.

The  load break switches can be equipped with earthing switches. The earthing switch has the same short - circuit making capacity as the load break switch, as well as the dynamic and thermal stability capability, and has a strict mechanical interlock with the load break switch, ensuring that misoperation is impossible in terms of structure.

 

Key Features

  • When the FKN12 - 12 load break switch is equipped with a high - voltage current - limiting fuse (with a striker) to form a load break switch - fuse combination, it serves as overload and short - circuit protection for loads (such as power transformers). When one or more phases of the fuse blow, the three phases of the load break switch automatically open.

  • The high - voltage load break switch is suitable for installation in ring - main unit switch cabinets and other types of switch cabinets for receiving and distributing electrical energy.

Technical Parameters

Serial No.

Name

Unit

Value

1

Rated Voltage

KV

12

2

Rated Frequency

Hz

50

3

Rated Current

A

630

4

Maximum Rated Current of Fuse

A

100

5

Rated Active Load Breaking Current, Rated Closed - loop Breaking Current

A

630

6

Rated Short - time Withstand Current (2S)

KA

20

7

Rated Short - circuit Making Current, Rated Peak Withstand Current

KA

50

8

1min Power Frequency Withstand Voltage, Phase - to - phase and to - ground / Break

KV

42/48

9

Lightning Impulse Withstand Voltage (Peak Value), Phase - to - phase and to - ground / Break

KV

75/85

10

Rated Cable Charging Breaking Current

A

10

11

Rated Breaking of No - load Transformer

KVA

1250

12

Mechanical Life

Times

2000

13

Rated Breaking Transfer Current

A

1150

14

Rated Short - circuit Breaking Current of Fuse

KA

31.5

Main Mechanical Characteristics of Load Break Switch

Serial No.

Name

Unit

Value

Remarks

1

Phase - to - phase Center Distance

mm

210 ± 3


2

Total Stroke of Conductive Rod

mm

215 ± 5

3

Distance Between Moving and Static Arc at Opening Position

mm

>160

4

Over - stroke of Electrical Contact of Moving Contact Rod

mm

42 ± 3

5

Just - Closing Speed

m/s

3.8 <sup>+0.7</sup><sub>-0.2</sub>

6

Just - Opening Speed

m/s

>2.7

7

Three - phase Closing Asynchronism

ms

>10

Contact between moving contact rod and contact fingers

8

Three - phase Opening Asynchronism

ms

>5

Separation between moving contact rod and contact fingers

Operating Environmental Conditions

  • Altitude: Not exceeding 1000m.

  • Ambient Temperature: Maximum +40&deg;C, Minimum -10&deg;C.

  • Relative Humidity: Daily average not exceeding 95%, Monthly average not exceeding 90%.

  • Seismic Intensity: Less than 8 degrees.

Know your supplier
ROCKWILL
Rockwill Electric Group Global Manufacturer of High voltage and medium-voltage power equipment and smart grid solutions. Headquartered in Wenzhou, China. Serving 100+ countries with quality, innovation, and trust. What We Offer: • HV-MV switchgear (VCB, SF₆ circuit breakers, RMU, GIS) • Distribution transformers and substations • Smart grid and monitoring systems • Solar, wind, EV charging, and energy storage solutions • EPC turnkey power projects Certified: ISO 9001 / ISO 14001 / ISO 45001
Main Categories
High voltage
Business Type
Design/Manufacture/Sales
Highest Annual Export (USD)
$150,000,000
Professional Experience
16 years
Workplace
108000m²m²
占位
占位
Related Products
Related Knowledges
Installation and Commissioning of 10kV Dry-Type Transformers
Installation and Commissioning of 10kV Dry-Type Transformers
By James, 10 Years of Electrical Equipment Maintenance ExperienceHi everyone, I’m James, and I’ve been working in electrical equipment fault repair for 10 years.Over the past decade, I’ve worked in factories, substations, and distribution rooms of all sizes, involved in the installation, commissioning, maintenance, and troubleshooting of dry-type transformers. Dry-type transformers are among the most common electrical devices we deal with on a daily basis.Today, a new colleague
James
07/01/2025
What are the reasons for low insulation at the low-voltage side of a dry-type transformer?
What are the reasons for low insulation at the low-voltage side of a dry-type transformer?
Hi everyone, I’m Felix, and I’ve been working in electrical equipment fault repair for 15 years.Over these years, I’ve traveled across factories, substations, and distribution rooms all over the country, troubleshooting and repairing all kinds of electrical equipment. Dry-type transformers are among the most common devices we deal with.Today, a friend asked me:“What does it mean when the low-voltage side of a dry-type transformer has low insulation resistance?”Great
Felix Spark
07/01/2025
What tests are required for dry-type transformers?
What tests are required for dry-type transformers?
1 Pre - commissioning InspectionAs a front - line tester, before formally commissioning a dry - type transformer, I need to carry out a comprehensive and systematic inspection. First, I conduct a visual inspection of the transformer body and its accessories, carefully checking for mechanical damage or deformation. Then, I check whether the leads of the high - and low - voltage windings are firmly connected and whether the bolt tightening torque meets the standard requirements (usually 40 - 60N&m
Oliver Watts
07/01/2025
What aspects need attention during the installation of dry-type transformers?
What aspects need attention during the installation of dry-type transformers?
1 Pre - installation PreparationAs a front - line installer, I know very well that the preparation work before installing a dry - type transformer must be thorough. First, I will carefully review the design drawings and technical documents, and check one by one the technical parameters such as the model specification, rated capacity, and voltage level of the transformer to ensure they are in full compliance with the design requirements. Then, I will conduct an unpacking inspection of the transfo
James
07/01/2025
What are the causes of dry-type transformers burning out during operation?
What are the causes of dry-type transformers burning out during operation?
1 Fault PhenomenonI am engaged in front - line fault maintenance work, and recently encountered problems with dry - type transformers. Dry - type transformers have a simple structure, are convenient for transportation, and easy for maintenance. They are widely used in power distribution places with relatively high environmental protection requirements. Because of their good fire - resistance, they can be installed in load - center areas to reduce voltage loss and power loss.The property manageme
Felix Spark
07/01/2025
Method for Automatic Isolation of Customer Equipment Faults by Load Switches in Distribution Networks
Method for Automatic Isolation of Customer Equipment Faults by Load Switches in Distribution Networks
1 OverviewDistribution network safety has long been under - addressed, with its automation lagging substation automation . Using 10 kV intervals of existing substations to set line section points meets future grid needs . Configuration of distribution switches, section switches, and protection must match substation outgoing - line protection for reliability. Fault isolation, self - healing, and restoration are key to distribution automation .Scholars have studied smart distribution network fault
Felix Spark
06/30/2025
×
Inquiry
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!