Brand | ROCKWILL |
Model NO. | DS22B 126kV 145kV 252kV 363kV 420kV 550kV High voltage disconnect switch |
Rated voltage | 550kV |
Rated normal current | 5000A |
Rated frequency | 50/60Hz |
Rated peak value withstand current | 160kA |
Rated short-time withstand current | 63kA |
Series | DS22B |
Product introduction
DS22B Switch Disconnector is a kind of outdoor HV electricity transmission equipment at three-phase AC frequency of 50Hz/60Hz. it is used for breaking or connecting HV lines under no loads so that these lines can be changed and connected and the way he electricity runs is changed, in addition, it can be used to exercise safe electrical insulation for such HV electric apparatuses as bus and breaker. The switch can open and close inductance/capacitance current and is able to open and close the bus to switch current.
This product is in the single-post single arm vertical telescopic structure. The contact is of the forceps-type, Vertical insulating breaks will be formed after the opening. The product can be used as an disconnect switch for bus. it is directly installed directly under the bus and only occupies a small space. JW10 earthing switch can be attached for grounding the bus at the lower layer, The grounding for the bus at the upper layer requires an independent earthing switch. 363kV and 550kV switch Disconnector and earthing switch are equipped with the SRCJ2 motor actuator for the single pole operation, Meanwhile, the tre-pole linkage can be achieved, The 126kV and 252kV isolating switches adopt SRCJ7 and SRCJ3 motor-based actuators to realize the tri-pole linkage. The grounding switch adopts CS11 and SRCS manual actuators to actualize tri-pole linkage.
This switch Disconnector has passed the verification by the review procedure organized by China Machinery industry federation that the product structure and performance satisfy the requirements on perfection, and product's performance indices have reached the internal level of the same kinds of products.
DS22B switch Disconnector comprises three single poles and actuator, Each single pole is made of a base, post insulator operating insulator and conductive part. The conductive part includes the gear box and foldable conductive arm fixed on the top of the post insulator, and the fixed contact hanging on the overload bus.
The actuator drives the operating insulator, and through the ink lever-driven conducive arm, if and lower the insulator to tighten or separate the moving contact and fixed contact on the directly overhead bus line to open or close the disconnect switch. After the opening, a vertical insulating break will be formed.
Main characteristic
Main technical parameters
Order notice
Product model, rated voltage, rated current, rated short-time withstand current and creepage distance must be specified at the goods-ordering time;
It can be decided whether a earthing switch should be attached to the switch Disconnector;
It must be decided whether the upper bus line of the switch Disconnector is soft or hard. Additionally, the external diameter of the tubular busbar shall be specified;
It must be decided whether the disconnect switch is arranged in cross-over or parallel form;
The actuator's model, motor's voltage, control voltage and the number of contacts for auxiliary switch.