• Complete Set of Large Capacity 160kA Generator Circuit Breaker
Complete Set of Large Capacity 160kA Generator Circuit Breaker
discuss personally
Model
ZHN10-24 /27000-160
Basic info
Brand ROCKWILL
Model NO. Complete Set of Large Capacity 160kA Generator Circuit Breaker
Rated voltage 24kV
Rated normal current 27000A
Series Circuit Breaker
Product Detail

Description:

This product is suitable for water, thermal power, and nuclear power units with a single generator capacity of 600-800 megawatts. The rated short-circuit breaking current is 160 kiloamperes, and the rated peak withstand current is 440 kiloamperes. In 2013, it was appraised by the China Machinery Industry Federation and successfully applied in the Xiangjiaba project, achieving complete localization, making China one of the few countries in the world capable of producing large capacity generator circuit breakers, and reducing engineering procurement costs for domestic users.

Product Performance:

  • Implemented according to the latest IEC standards.

  • High insulation level: meeting the insulation requirements of the products under the environment of 3,000m above sea level.

  • High long-term flow capacity: adopts natural cooling, no auxiliary heat dissipation device, the rated flow capacity up to 25,000A. With forced air cooling by fan, the rated flow capacity up to 27,000A.

  • Excellent 0breaking performance: the effective value of Ac component of short-circuit breaking current has is 160kA and the DC component is as high as 87%, which meets the current breaking requirements under various fault conditions.

  • High mechanical reliability: Innovative design of circuit breaker drive ensures that the product can meet the breaking performance under the small input operation power, and realize the mechanical life requirement of operation for 5,000times, Disconnector and earthing switch meet the mechanical life requirement of operation for 10,000 times.

  • Comprehensive safety protection measures: Pressure release device is installed at the top of the circuit breaker. When the gas pressure in the arc extinguishing chamber exceeds 1.2MPa due to an accident, the gas will be released to ensure the safety of the personnel and surrounding equipment. The product design can ensure the stable operation of the power plant.

Product Structure:

  • The product consists of three single poles, and each pole has an individual enclosed metal enclosure mounted on the same chassis.

  • Circuit breaker is equipped with hydraulic spring operating mechanism; The disconnector and earthing switch are equipped with motor operating mechanism; The driving modes are all three-phase mechanical linkage.

  • Each operating mechanism is installed on the side of the product close to the control cabinet.

  • SF6 is used as internal insulation and arc-extinguishing medium for circuit breaker, and adopts self-energy arc extinguishing principle. It is mainly composed of the main contact system, arc extinguishing system and driving system.

  • Air is used as insulation medium to isolate the break of the disconnector, the isolation moving contact adopts telescopic direct-acting structure, and the fixed contact adopts inner and outer two-layer contact finger structures, when closing, both the inner and outer surfaces of the moving contact are in contact with the contact finger, thus ensuring sufficient current capacity. Double guiding devices are used to ensure smooth closing of the moving contact.

  • Air is used as insulation medium to isolate the break of the earthing switch. The fixed contact is installed on the support of the main circuit, and the moving contact is installed on the bottom plate of the single pole enclosure.
    微信图片_20240615104546_修复后.png

Typical applications:
微信图片_20240615104629_修复后.png
微信图片_20240615104649_修复后.png

160kA intelligent generator circuit breaker:
微信图片_20240615104608_修复后.png

160 kA intelligent generator circuit breaker not only has basic protection function, but also integrates potential transformer, current transformer, lightning arrester and other components. Each product is equipped with a set of intelligent on-line monitoring device to realize on-line monitoring of conductor temperature, mechanical characteristics of circuit breaker, SF6 gas condition and so on.
Main technical parameters:

image.png

What are the technical parameters of generator circuit breaker?

Rated Voltage:

  • This is the highest voltage at which the generator circuit breaker can operate normally. For example, for generator circuit breakers in large thermal power plants, the rated voltage may reach 20 - 30 kV or even higher. This parameter must match the rated output voltage of the generator to ensure safe and reliable operation under both normal and fault conditions.

Rated Current:

  • It indicates the maximum current that the generator circuit breaker can carry continuously. The selection of the rated current should be based on the rated capacity of the generator. For instance, a 100 MW generator may have a rated current in the range of several thousand amperes, and the rated current of the generator circuit breaker needs to meet this requirement to ensure it can handle the generator's output current during normal operation.

Short-Circuit Breaking Capacity:

  • This is a critical parameter that measures the ability of the generator circuit breaker to interrupt short-circuit faults. When a short circuit occurs at the generator outlet or on the grid side, the circuit breaker must be able to quickly interrupt the high short-circuit current to prevent the fault from spreading. For example, in large power plants, the short-circuit breaking capacity of the generator circuit breaker may reach tens of kiloamperes or even higher, requiring the breaker to have strong arc-quenching capabilities and good thermal and dynamic stability.

Making Current:

  • The making current refers to the maximum instantaneous current that the circuit breaker can withstand when it is closed. During generator startup or when the grid recovers after a fault, there may be significant inrush currents. The circuit breaker must be able to safely close these currents; otherwise, it could result in issues such as contact welding.


Know your supplier
ROCKWILL
Rockwill Electric Group Global Manufacturer of High voltage and medium-voltage power equipment and smart grid solutions. Headquartered in Wenzhou, China. Serving 100+ countries with quality, innovation, and trust. What We Offer: • HV-MV switchgear (VCB, SF₆ circuit breakers, RMU, GIS) • Distribution transformers and substations • Smart grid and monitoring systems • Solar, wind, EV charging, and energy storage solutions • EPC turnkey power projects Certified: ISO 9001 / ISO 14001 / ISO 45001
Main Categories
High voltage
Business Type
Design/Manufacture/Sales
Highest Annual Export (USD)
$150,000,000
Professional Experience
16 years
Workplace
108000m²m²
占位
占位
Related Products
Related Knowledges
Failure Analysis and Design Optimization of Conventional Grounding Transformers
Failure Analysis and Design Optimization of Conventional Grounding Transformers
I. Core Cause of Damage: Electrodynamic Impact (Complying with GB/T 1094.5 / IEC 60076-5)The direct cause of high-voltage winding end collapse is the instantaneous electrodynamic impact induced by short-circuit current. When a single-phase grounding fault occurs in the system (such as lightning overvoltage, insulation breakdown, etc.), the grounding transformer, as the fault current path, withstands high-amplitude and steep-rise-rate short-circuit currents. According to Ampère's force law
Felix Spark
06/12/2025
Analysis of Grounding Transformer Operational Behavior Under System Single-Phase-to-Ground Fault Conditions
Analysis of Grounding Transformer Operational Behavior Under System Single-Phase-to-Ground Fault Conditions
1 Theoretical AnalysisIn distribution networks, grounding transformers serve two key roles: powering low - voltage loads and connecting arc - suppression coils at neutrals for grounding protection. Grounding faults, the most common distribution network fault, heavily impact transformers’ operating characteristics, causing sharp changes in electromagnetic parameters and status.To study transformers’ dynamic behaviors under single - phase grounding faults, build this model: Assume a tr
Felix Spark
06/12/2025
Design Calculations for Neutral Grounding Schemes and Grounding Transformer Sizing in Utility-Scale Solar PV Plants
Design Calculations for Neutral Grounding Schemes and Grounding Transformer Sizing in Utility-Scale Solar PV Plants
1 Classification of Neutral Grounding Methods for Solar Photovoltaic Power StationsInfluenced by differences in voltage levels and grid structures across regions, the neutral grounding methods of power systems are mainly categorized into non-effective grounding and effective grounding. Non-effective grounding includes neutral grounding via arc suppression coils and neutral ungrounded systems, while effective grounding comprises neutral solid grounding and neutral grounding via resistors. The sel
Dyson
06/12/2025
Zero-Sequence Impedance Characterization of Dry-Type Grounding Transformer with ZN Connection
Zero-Sequence Impedance Characterization of Dry-Type Grounding Transformer with ZN Connection
In a neutral-insulated three-phase power system, an earthing transformer provides an artificial neutral point, which can be solidly earthed or earthed via reactors/arc suppression coils. The ZNyn11 connection is typical, where zero-sequence magnetomotive forces in the inner/outer half-windings of the same core column cancel out, balancing fault currents in series windings and minimizing zero-sequence leakage flux/impedance.Zero-sequence impedance is critical: it determines fault current magnitud
Dyson
06/12/2025
Case Analysis on Maloperation of Grounding Transformer Overcurrent Protection Relay
Case Analysis on Maloperation of Grounding Transformer Overcurrent Protection Relay
The neutral grounding mode refers to the connection between the power system neutral point and ground. In China's 35 kV and below systems, common methods include ungrounded neutral, arc-suppression coil grounding, and small-resistance grounding. The ungrounded mode is widely used as it allows short-term operation during single-phase grounding faults, while small-resistance grounding has become mainstream for its fast fault removal and overvoltage limitation. Many substations install grounding tr
Felix Spark
06/12/2025
Discussion on the Design of Low Zero-Sequence Impedance Grounding Transformers
Discussion on the Design of Low Zero-Sequence Impedance Grounding Transformers
With the expansion of power system scale and the cableization process of urban power grids, the capacitive current in 6kV/10kV/35kV power grids has significantly increased (generally exceeding 10A). As power grids at this voltage level mostly adopt neutral ungrounded operation mode, and the distribution voltage side of main transformers is usually in delta connection, lacking a natural grounding point, the arc during ground faults cannot be reliably extinguished, necessitating the introduction o
Dyson
06/11/2025
×
Inquiry
Download