• Complete Set of Large Capacity 100kA Generator Circuit Breaker
Complete Set of Large Capacity 100kA Generator Circuit Breaker
discuss personally
Model
ZHN10-24/15000-120
Basic info
Brand ROCKWILL
Model NO. Complete Set of Large Capacity 100kA Generator Circuit Breaker
Rated voltage 24kV
Rated normal current 15000
Series Circuit Breaker
Product Detail

Description:

This product is suitable for water and thermal power plants with a single generator unit capacity of 300-400 megawatts. It has a large current carrying capacity and strong breaking capacity. It was appraised by the China Machinery Industry Federation in 2019, and its comprehensive technical performance has reached the international leading level. Currently, it has supplied multiple power plants.

Product Performance:

  • Implemented according to the latest lEC standards.

  • High insulation level: meeting the insulation requirements of the products under the environment of 3,000m above sea level.

  • High long-term flow capacity: adopts natural cooling, no auxiliary heat dissipation device, and rated flow capacity up to 15,000A.

  • Excellent breaking performance: The effective values of Ac component of short-circuit breaking current is 100kA and the DC component is as high as 82%, which meets the current breaking requirements under various fault conditions.

  • High mechanical reliability: Innovative design of circuit breaker drive ensures that the product can meet the breaking performance under the small input operation work, and realize the mechanical life requirement of operation for 10,000times.

  • Comprehensive safety protection measures: Pressure release device is installed at the top of the circuit breaker When the gas pressure in the arc extinguishing chamber exceeds 1.2Pa due to an accident, the gas will be released to ensure the safety of the personnel and surrounding equipment, The product design can ensure the stable operation of the power plant.

Product Structure:

  • The product consists of three single poles, and each pole has an individual enclosed metal enclosure mounted on the same chassis.

  • Circuit breaker is equipped with hydraulic spring operating mechanism: the disconnector and earthing switch are equipped with motor operating mechanism; the driving modes are all three phase mechanical linkage.

  • The main circuit adopts natural cooling.

  • Each operating mechanism is installed on the side of the product close to the control cabinet.

  • SF6 is used as arc extinguishing and insulation medium for circuit breaker, and the arc extinguishing chamber adopts a new type of arc extinguishing chamber which combines self-energy arc extinguishing with auxiliary air-compressor arc extinguishing, which effectively reduces the operating work and perfectly solves the problem of short-circuit current breaking of various energies.

  • The disconnector and the circuit breaker are connected in series, arranged in the same enclosure, using the air as the insulation medium, the fixed contact is located at the circuit breaker side, and the moving contact is in the telescopic direct-acting structure, which has the advantages of simple structure with small occupancy size and high current capability.

  • The earthing switches are arranged on both sides of the incoming and cut going lines respectively, and using the air as the insulation medium, The fixed contacts are located on the high potential side, which are installed on the support of the main circuit, and the moving side is installed on the bottom plate of the box body. The moving contacts are connected with the single-phase enclosure and form earthing loop through the metal-enclosed isolated phase busbars connected with the moving contacts.
    微信图片_20240615104709_修复后.png

Typical applications:
微信图片_20240615104755_修复后.png

微信图片_20240615104813_修复后.png

Main technical parameters:

image.png

What is a generator circuit breaker?

A generator circuit breaker is a special type of circuit breaker used to connect a generator to the power grid system. Its primary functions are to control the synchronization and disconnection of the generator with the grid under normal conditions, which means it enables the connection and disconnection of the generator to and from the grid. For example, once the generator starts up and reaches its rated parameters, the generator circuit breaker is used to connect it to the grid, allowing the generator to begin supplying electrical power to the grid. Additionally, in the event of a generator fault (such as a short circuit or overload) or a grid-side fault that could affect the safe operation of the generator, the generator circuit breaker can quickly disconnect the electrical connection between the generator and the grid, thereby protecting both the generator and the grid system.

Know your supplier
ROCKWILL
Rockwill Electric Group Global Manufacturer of High voltage and medium-voltage power equipment and smart grid solutions. Headquartered in Wenzhou, China. Serving 100+ countries with quality, innovation, and trust. What We Offer: • HV-MV switchgear (VCB, SF₆ circuit breakers, RMU, GIS) • Distribution transformers and substations • Smart grid and monitoring systems • Solar, wind, EV charging, and energy storage solutions • EPC turnkey power projects Certified: ISO 9001 / ISO 14001 / ISO 45001
Main Categories
High voltage
Business Type
Design/Manufacture/Sales
Highest Annual Export (USD)
$150,000,000
Professional Experience
16 years
Workplace
108000m²m²
占位
占位
Related Products
Related Knowledges
Failure Analysis and Design Optimization of Conventional Grounding Transformers
Failure Analysis and Design Optimization of Conventional Grounding Transformers
I. Core Cause of Damage: Electrodynamic Impact (Complying with GB/T 1094.5 / IEC 60076-5)The direct cause of high-voltage winding end collapse is the instantaneous electrodynamic impact induced by short-circuit current. When a single-phase grounding fault occurs in the system (such as lightning overvoltage, insulation breakdown, etc.), the grounding transformer, as the fault current path, withstands high-amplitude and steep-rise-rate short-circuit currents. According to Ampère's force law
Felix Spark
06/12/2025
Analysis of Grounding Transformer Operational Behavior Under System Single-Phase-to-Ground Fault Conditions
Analysis of Grounding Transformer Operational Behavior Under System Single-Phase-to-Ground Fault Conditions
1 Theoretical AnalysisIn distribution networks, grounding transformers serve two key roles: powering low - voltage loads and connecting arc - suppression coils at neutrals for grounding protection. Grounding faults, the most common distribution network fault, heavily impact transformers’ operating characteristics, causing sharp changes in electromagnetic parameters and status.To study transformers’ dynamic behaviors under single - phase grounding faults, build this model: Assume a tr
Felix Spark
06/12/2025
Design Calculations for Neutral Grounding Schemes and Grounding Transformer Sizing in Utility-Scale Solar PV Plants
Design Calculations for Neutral Grounding Schemes and Grounding Transformer Sizing in Utility-Scale Solar PV Plants
1 Classification of Neutral Grounding Methods for Solar Photovoltaic Power StationsInfluenced by differences in voltage levels and grid structures across regions, the neutral grounding methods of power systems are mainly categorized into non-effective grounding and effective grounding. Non-effective grounding includes neutral grounding via arc suppression coils and neutral ungrounded systems, while effective grounding comprises neutral solid grounding and neutral grounding via resistors. The sel
Dyson
06/12/2025
Zero-Sequence Impedance Characterization of Dry-Type Grounding Transformer with ZN Connection
Zero-Sequence Impedance Characterization of Dry-Type Grounding Transformer with ZN Connection
In a neutral-insulated three-phase power system, an earthing transformer provides an artificial neutral point, which can be solidly earthed or earthed via reactors/arc suppression coils. The ZNyn11 connection is typical, where zero-sequence magnetomotive forces in the inner/outer half-windings of the same core column cancel out, balancing fault currents in series windings and minimizing zero-sequence leakage flux/impedance.Zero-sequence impedance is critical: it determines fault current magnitud
Dyson
06/12/2025
Case Analysis on Maloperation of Grounding Transformer Overcurrent Protection Relay
Case Analysis on Maloperation of Grounding Transformer Overcurrent Protection Relay
The neutral grounding mode refers to the connection between the power system neutral point and ground. In China's 35 kV and below systems, common methods include ungrounded neutral, arc-suppression coil grounding, and small-resistance grounding. The ungrounded mode is widely used as it allows short-term operation during single-phase grounding faults, while small-resistance grounding has become mainstream for its fast fault removal and overvoltage limitation. Many substations install grounding tr
Felix Spark
06/12/2025
Discussion on the Design of Low Zero-Sequence Impedance Grounding Transformers
Discussion on the Design of Low Zero-Sequence Impedance Grounding Transformers
With the expansion of power system scale and the cableization process of urban power grids, the capacitive current in 6kV/10kV/35kV power grids has significantly increased (generally exceeding 10A). As power grids at this voltage level mostly adopt neutral ungrounded operation mode, and the distribution voltage side of main transformers is usually in delta connection, lacking a natural grounding point, the arc during ground faults cannot be reliably extinguished, necessitating the introduction o