• 40.5kV 72.5kV 145 kV 252kV Series Dead Tank circuit breaker
  • 40.5kV 72.5kV 145 kV 252kV Series Dead Tank circuit breaker
40.5kV 72.5kV 145 kV 252kV Series Dead Tank circuit breaker
discuss personally
Model
LW58A-252/4000-50
LW58A-145/3150-40
LW58A-72.5/4000-40
LW58A-72.5/4000-31.5
LW58A-72.5/3150-40
LW58A-72.5/3150-31.5
LW58A-72.5/2500-40
LW58A-72.5/2500-31.5
LW58A-40.5/4000-40
LW58A-40.5/4000-31.5
LW58A-40.5/3150-40
LW58A-40.5/3150-31.5
LW58A-40.5/2500-40
LW58A-40.5/2500-31.5
Basic info
Brand Wone
Model NO. LW58A Series Dead Tank circuit breaker
Rated voltage 252kV
Rated normal current 4000A
Rated frequency 50/60Hz
Rated short circuit breaking current 50kA
Series LW58A-40.5(72.5)(145)(252)
Product Detail

Product introduction:

LW58A-40.5/72.5/145/252 Dead Tank circuit breaker is a new generation of open high-voltage electrical equipment developed independently ,The tank type circuit breaker is composed of the entrance bushing, lead-out bushing, CT, arc extinguishing chamber, chassis, operating mechanism, etc. It can be used in the high-cold and high-altitude area, At present, the new generation of tank type LW58A-40.5/72.5 products have reached the leading domestic and international advanced level in advanced technology and quality reliability.

Main characteristic:

  •  Good anti-seismic performance, the product is equivalent to the seismic grade of GlS.

    (a)Horizontal arrangement of arc extinguishing chamber, low center of gravity.

    (b)Auto seismic frequency: The porcelain column breaker is about 4.5 Hz, and the tank circuit breaker is about 13.5 Hz.

  • The electric tracing band solution can be used in the high-cold region, which can not be realized by the porcelain column circuit breaker.

  • The product can be used in an area of 5000m , the standard configuration of the arc extinguishing chamber & drive system can only be fixed with the height of the outlet casing.

  •  The tank type circuit breakers integrates the straight through current transformer, the product covers a small area the quality is stable, and the on-site maintenance work is small. At the same time, it solves the problems such as the small margin of CT insulation ,the limitation of CT capacity and the high cost ,aging, cracking and explosion of the CT.

  •  Design of an arc extinguishing chamber:Horizontal Structure, it adopts thermal expansion and auxiliary pressure gas extinguishing technology, which has small operation work, excellent breaking performance and more than 20 electrical life.

  • Environment adaptability:It is suitable for severe environment conditions (such as severe pollution, water fog, hall, etc.), high - altitude area, high altitude area, earthquake area, the box body is sealed with air bag type, and the body protection grade is lP66.

  • The CT of variable ratio and multi-level combination can be attached, high accuracy, easy to add capacity, and meet 80% or the operating frequency voltage under the value of 5Pc, can be configured with TPY.

  •  Complete CT protection measures: CT shell is sealed at both ends of the shell and has special ant-condensation design.

  • The light spring operating mechanism adopts the overall cast aluminum frame. Breaking spring , closing spring and buffer are arranged in a centralized manner, and all adopt spiral double pressure spring, compact structure, not easy to fatigue.

  • The product is small, with integrated design, integrated supply, integrated installation conditions.

  • With the breaking capacity of the 4000A back-to-back capacitor bank.

Main technical parameters:

image.png

Order Notice:

  • Model and format of circuit breaker.

  • Rated electrical parameters (voltage, current, break current, etc).

  • Working conditions for using (environment temperature, altitude, and environment pollution level).

  • Operating voltage of operating mechanism and motor voltage.

  • The number of current transformer, current ratio, class combination and secondary load.

  • Names and quantities of spare items needed, parts and special equipment and tools(to be otherwise ordered).

What are the structural characteristics of the tank circuit breaker?

Integral Tank Structure:

  • Integral Tank Structure: The breaker's arc quenching chamber, insulating medium, and related components are sealed within a metal tank filled with an insulating gas (such as sulfur hexafluoride) or insulating oil. This forms a relatively independent and sealed space, effectively preventing external environmental factors from affecting the internal components. This design enhances the insulation performance and reliability of the equipment, making it suitable for various harsh outdoor environments.

Arc Quenching Chamber Layout:

  • Arc Quenching Chamber Layout: The arc quenching chamber is typically installed inside the tank. Its structure is designed to be compact, enabling efficient arc quenching within a limited space. Depending on different arc quenching principles and technologies, the specific construction of the arc quenching chamber may vary, but generally includes key components such as contacts, nozzles, and insulating materials. These components work together to ensure that the arc is quickly and effectively extinguished when the breaker interrupts the current.

Operating Mechanism:

  • Operating Mechanism: Common operating mechanisms include spring-operated mechanisms and hydraulic-operated mechanisms.

  • Spring-Operated Mechanism: This type of mechanism is simple in structure, highly reliable, and easy to maintain. It drives the opening and closing operations of the breaker through the energy storage and release of springs.

  • Hydraulic-Operated Mechanism: This mechanism offers advantages such as high output power and smooth operation, making it suitable for high-voltage and high-current class breakers.


Know your supplier
Wone
Main Categories
High voltage/Low voltage/Wire cable/Instrument meters/New energy/Tester/Production equipment/Generator/Electrical fittings/Integrated Electrical Equipment
Business Type
Design/Manufacture/Sales
Highest Annual Export (USD)
$50,000,000
Professional Experience
1 years
Workplace
65666m²m²
占位
占位
Related Products
Related Knowledges
Failure Analysis and Design Optimization of Conventional Grounding Transformers
Failure Analysis and Design Optimization of Conventional Grounding Transformers
I. Core Cause of Damage: Electrodynamic Impact (Complying with GB/T 1094.5 / IEC 60076-5)The direct cause of high-voltage winding end collapse is the instantaneous electrodynamic impact induced by short-circuit current. When a single-phase grounding fault occurs in the system (such as lightning overvoltage, insulation breakdown, etc.), the grounding transformer, as the fault current path, withstands high-amplitude and steep-rise-rate short-circuit currents. According to Ampère's force law
Felix Spark
06/12/2025
Analysis of Grounding Transformer Operational Behavior Under System Single-Phase-to-Ground Fault Conditions
Analysis of Grounding Transformer Operational Behavior Under System Single-Phase-to-Ground Fault Conditions
1 Theoretical AnalysisIn distribution networks, grounding transformers serve two key roles: powering low - voltage loads and connecting arc - suppression coils at neutrals for grounding protection. Grounding faults, the most common distribution network fault, heavily impact transformers’ operating characteristics, causing sharp changes in electromagnetic parameters and status.To study transformers’ dynamic behaviors under single - phase grounding faults, build this model: Assume a tr
Felix Spark
06/12/2025
Design Calculations for Neutral Grounding Schemes and Grounding Transformer Sizing in Utility-Scale Solar PV Plants
Design Calculations for Neutral Grounding Schemes and Grounding Transformer Sizing in Utility-Scale Solar PV Plants
1 Classification of Neutral Grounding Methods for Solar Photovoltaic Power StationsInfluenced by differences in voltage levels and grid structures across regions, the neutral grounding methods of power systems are mainly categorized into non-effective grounding and effective grounding. Non-effective grounding includes neutral grounding via arc suppression coils and neutral ungrounded systems, while effective grounding comprises neutral solid grounding and neutral grounding via resistors. The sel
Dyson
06/12/2025
Zero-Sequence Impedance Characterization of Dry-Type Grounding Transformer with ZN Connection
Zero-Sequence Impedance Characterization of Dry-Type Grounding Transformer with ZN Connection
In a neutral-insulated three-phase power system, an earthing transformer provides an artificial neutral point, which can be solidly earthed or earthed via reactors/arc suppression coils. The ZNyn11 connection is typical, where zero-sequence magnetomotive forces in the inner/outer half-windings of the same core column cancel out, balancing fault currents in series windings and minimizing zero-sequence leakage flux/impedance.Zero-sequence impedance is critical: it determines fault current magnitud
Dyson
06/12/2025
Case Analysis on Maloperation of Grounding Transformer Overcurrent Protection Relay
Case Analysis on Maloperation of Grounding Transformer Overcurrent Protection Relay
The neutral grounding mode refers to the connection between the power system neutral point and ground. In China's 35 kV and below systems, common methods include ungrounded neutral, arc-suppression coil grounding, and small-resistance grounding. The ungrounded mode is widely used as it allows short-term operation during single-phase grounding faults, while small-resistance grounding has become mainstream for its fast fault removal and overvoltage limitation. Many substations install grounding tr
Felix Spark
06/12/2025
Discussion on the Design of Low Zero-Sequence Impedance Grounding Transformers
Discussion on the Design of Low Zero-Sequence Impedance Grounding Transformers
With the expansion of power system scale and the cableization process of urban power grids, the capacitive current in 6kV/10kV/35kV power grids has significantly increased (generally exceeding 10A). As power grids at this voltage level mostly adopt neutral ungrounded operation mode, and the distribution voltage side of main transformers is usually in delta connection, lacking a natural grounding point, the arc during ground faults cannot be reliably extinguished, necessitating the introduction o