• Vacuum Circuit Breaker 24 kV , the next generation of HVX digital MV Circuit Breaker
Vacuum Circuit Breaker 24 kV , the next generation of HVX digital MV Circuit Breaker
discuss personally
Model
PacT Series EvoPacT HVX-24
Basic info
Brand Schneider
Model NO. Vacuum Circuit Breaker 24 kV , the next generation of HVX digital MV Circuit Breaker
Rated voltage 24kV
Series PacT Series EvoPacT HVX
Product Detail

Overview

EvoPacT HVX is a range of Vacuum Circuit Breakers (VCB), addressing 24 kV networks, with up to 31.5 kA short circuit capacities and ranging from 630 A to 2500 A. It is designed for use in Medium Voltage switchgear to connect primary power distribution consumers to the power grid. EvoPacT HVX digital circuit breakers are designed with more than 45 years of medium-voltage experience and manufactured using in-house, best-in-class components for a longer operational life. With innovative features, EvoPacT HVX uses digital features to help mitigate risks for facilities and the people who work in them

General characteristics

According to IEC 62271-100:2021
Main electrical characteristics:

 

Operating conditions

According to IEC 62271-100:2021
Main electrical characteristics:

Other service conditions

If operated beyond the normal service conditions, the circuit breaker is submitted to accelerated aging. The circuit breaker may only be used under conditions other than the normal service conditions with express written permission from Schneider Electric.

Storage

In order to preserve all of the device’s characteristics when stored for prolonged periods, we recommend to store the device in its original packaging, in dry conditions and sheltered from the sun and rain at a temperature between -40 °C and +70 °C. The maximum storage period is 12 months.

If the device was stored:

  •  Between 6 and 12 months: perform basic preventive maintenance to help ensure correct device operation
  •  Beyond 12 months: contact your Schneider Electric Service local representative  for device check-up

 

Fixed Circuit Breaker dimensions

 

Withdrawable Circuit Breaker dimensions

 

Modules description

Know your supplier
Schneider
Chengdu Fabo Automation Complete Equipment Co., Ltd is an authorized distributor of Schneider Electric, a global leader in energy management and automation solutions.
Main Categories
High voltage/Low voltage
Business Type
Manufacture/Sales
Highest Annual Export (USD)
$400000000
Professional Experience
9 years
Workplace
20000m²
占位
占位
Related Products
Related Knowledges
Failure Analysis and Design Optimization of Conventional Grounding Transformers
Failure Analysis and Design Optimization of Conventional Grounding Transformers
I. Core Cause of Damage: Electrodynamic Impact (Complying with GB/T 1094.5 / IEC 60076-5)The direct cause of high-voltage winding end collapse is the instantaneous electrodynamic impact induced by short-circuit current. When a single-phase grounding fault occurs in the system (such as lightning overvoltage, insulation breakdown, etc.), the grounding transformer, as the fault current path, withstands high-amplitude and steep-rise-rate short-circuit currents. According to Ampère's force law
Felix Spark
06/12/2025
Analysis of Grounding Transformer Operational Behavior Under System Single-Phase-to-Ground Fault Conditions
Analysis of Grounding Transformer Operational Behavior Under System Single-Phase-to-Ground Fault Conditions
1 Theoretical AnalysisIn distribution networks, grounding transformers serve two key roles: powering low - voltage loads and connecting arc - suppression coils at neutrals for grounding protection. Grounding faults, the most common distribution network fault, heavily impact transformers’ operating characteristics, causing sharp changes in electromagnetic parameters and status.To study transformers’ dynamic behaviors under single - phase grounding faults, build this model: Assume a tr
Felix Spark
06/12/2025
Design Calculations for Neutral Grounding Schemes and Grounding Transformer Sizing in Utility-Scale Solar PV Plants
Design Calculations for Neutral Grounding Schemes and Grounding Transformer Sizing in Utility-Scale Solar PV Plants
1 Classification of Neutral Grounding Methods for Solar Photovoltaic Power StationsInfluenced by differences in voltage levels and grid structures across regions, the neutral grounding methods of power systems are mainly categorized into non-effective grounding and effective grounding. Non-effective grounding includes neutral grounding via arc suppression coils and neutral ungrounded systems, while effective grounding comprises neutral solid grounding and neutral grounding via resistors. The sel
Dyson
06/12/2025
Zero-Sequence Impedance Characterization of Dry-Type Grounding Transformer with ZN Connection
Zero-Sequence Impedance Characterization of Dry-Type Grounding Transformer with ZN Connection
In a neutral-insulated three-phase power system, an earthing transformer provides an artificial neutral point, which can be solidly earthed or earthed via reactors/arc suppression coils. The ZNyn11 connection is typical, where zero-sequence magnetomotive forces in the inner/outer half-windings of the same core column cancel out, balancing fault currents in series windings and minimizing zero-sequence leakage flux/impedance.Zero-sequence impedance is critical: it determines fault current magnitud
Dyson
06/12/2025
Case Analysis on Maloperation of Grounding Transformer Overcurrent Protection Relay
Case Analysis on Maloperation of Grounding Transformer Overcurrent Protection Relay
The neutral grounding mode refers to the connection between the power system neutral point and ground. In China's 35 kV and below systems, common methods include ungrounded neutral, arc-suppression coil grounding, and small-resistance grounding. The ungrounded mode is widely used as it allows short-term operation during single-phase grounding faults, while small-resistance grounding has become mainstream for its fast fault removal and overvoltage limitation. Many substations install grounding tr
Felix Spark
06/12/2025
Discussion on the Design of Low Zero-Sequence Impedance Grounding Transformers
Discussion on the Design of Low Zero-Sequence Impedance Grounding Transformers
With the expansion of power system scale and the cableization process of urban power grids, the capacitive current in 6kV/10kV/35kV power grids has significantly increased (generally exceeding 10A). As power grids at this voltage level mostly adopt neutral ungrounded operation mode, and the distribution voltage side of main transformers is usually in delta connection, lacking a natural grounding point, the arc during ground faults cannot be reliably extinguished, necessitating the introduction o
Dyson
06/11/2025
×
Inquiry
Download