I. Definitions of Losses in IEC 6007
IEC 60076-1 (General Requirements) and IEC 60076-7 (Loading Guidelines) specify two core types of losses:
No-load Loss (P0)
Definition: Losses measured when the primary winding is energized at rated voltage and the secondary winding is open-circuited (dominated by core losses).
Test Conditions
Load Loss (Pk)
Definition: Losses measured when the secondary winding is short-circuited and rated current flows through the primary winding (dominated by copper losses).
Test Conditions:
II. Testing and Calculation of Losses
No-load Loss Test (IEC 60076-1 Clause 10)
Method
Temperature Correction Formula:
Bref: Flux density at reference temperature; B test : Measured flux density.
2. Load Loss Test (IEC 60076-1 Clause 11)
Method:
Temperature Correction Formula (for copper windings)
Tref: Reference temperature (75°C); T test : Winding temperature during testing.
Key Parameters and Tolerances
Loss Tolerances (IEC 60076-1 Clause 4.2):
Losses caused by leakage flux in structural components, evaluated via high-frequency component separation or thermal imaging.
Energy Efficiency Classes and Loss Optimization
Per IEC 60076-14 (Energy Efficiency Guidelines for Power Transformers):
Total Losses (P total):
β: Load ratio (actual load / rated load).
Efficiency Classes (e.g., IE4, IE5) require total losses reduced by 10%~30%, achieved via:
Practical Application Example
Case: 35kV Oil-Immersed Transformer (IEC 60076-7)
Rated Parameters:
Test Data:
No-load loss: 5.2 kW (within +15% tolerance → 5.75 kW limit).
Load loss (tested at 30°C):
Conclusion: Load loss exceeds tolerance? Verify against 50 × 1.15 = 57.5 kW.
VI. Common Issues and Considerations
Ambient Temperature:
Tests must be conducted between -25°C to +40°C; corrections required outside this range.
Harmonic Losses:
Evaluate additional harmonic losses under non-sinusoidal loads per IEC 60076-18.
Digital Testing:
Use IEC 61869-calibrated sensors for accuracy.