Parameter |
Value |
Notes |
Rated Voltage |
12kV |
- |
Rated Current |
630A, 800A, 1250A, 1600A |
Customizable |
Short-Circuit Breaking Capacity |
20kA, 25kA, 31.5kA |
Customizable |
Power-Frequency Withstand Voltage (1min) |
Dry: 48kV / Wet: 38kV |
DL/T403 Compliant |
Lightning Impulse Withstand Voltage |
75kV |
- |
Mechanical Life |
≥10,000 operations |
Spring mechanism, oil-free design |
Short-Time Withstand Current (4s) |
31.5kA |
- |
II. Applications & Compatibility
Cabinet Series |
Compatible Models |
Domestic Cabinets |
KYN28, KYN96, XGN series |
International Cabinets |
ABB ZS series |
Installation Type: Fixed (Lateral Type) |
III. Technical Advantages & Innovations
IV. Customization Services
Customization Item |
Options |
Insulation Medium |
Air-insulated / Gas-insulated (SF₆ alternative) |
Secondary Wiring Layout |
Front/Rear/Side wiring |
Special Current Ratings |
>1600A or >31.5kA designs |
High-altitude Adaptation |
≤2500m (derating required for higher elevations) |
V. Installation & Maintenance
VI. Typical Configurations (Examples)
Application Scenario |
Recommended Configuration |
Protection Target |
Substation Inlet Cabinet |
VSC-1250A/31.5kA + Motorized |
Main transformer short-circuit |
Industrial Distribution Center |
VSC-1600A/25kA + Rear Wiring |
Large motor control |
Commercial Complex |
VSC-800A/20kA + Front Wiring |
LV busbar segmentation |
VII. Support Services
Rockwill Electric Technical Guarantee: