Brand | ROCKWILL |
Model NO. | RCW-F38G 38kV outdoor vacuum recloser |
Rated voltage | 38kV |
Rated normal current | 630A |
Rated short circuit breaking current | 16kV |
Power frequency withstand voltage | 90kV/min |
Rated lightning impulse voltage | 195kV |
manual closing | No |
Mechanical lock | No |
Series | RCW |
Description:
The RCW series automatic circuit reclosers can use on overhead distribution lines as well as distribution substation applications for allvoltage classes 11kV up to 38kV at 50/60Hz power system. and it’s rated current can reach 1250A.The RCW series automatic circuit reclosers integrates the functions of control, protection, measurement, communication, fault detection, on-line monitoring of closing or opening.The RCW series vacuum recloser is mainly combined with integration terminal, current transformer, permanent magnetic actuator and it’s recloser controller.
Features:
Optional grades available in rated current range.
With optional relay protection and logic for user selection.
With optional communication protocols and I/O ports for users to choose.
PC software for controller testing, setup, programming, updates.
Parameters:
External dimensions:
Environmental requirement:
Product show:
What are the structural characteristics of outdoor vacuum recloser?
Vacuum Arc Quenching Chamber: The core component that uses a vacuum environment to extinguish arcs. It offers advantages such as strong breaking capacity, fast dielectric recovery, and long contact life, effectively ensuring the reliability of the equipment when interrupting fault currents.
Insulating Pillars: Typically made from high-strength, weather-resistant insulating materials such as epoxy resin, these pillars provide reliable insulation support for the vacuum arc quenching chamber and other components, ensuring the insulation performance of the equipment in harsh outdoor environments.
Operating Mechanism: Common types include spring-operated mechanisms and permanent magnet-operated mechanisms. Spring-operated mechanisms are simple in structure, highly reliable, and easy to maintain. Permanent magnet-operated mechanisms, on the other hand, offer advantages such as fast action, low energy consumption, and long mechanical life, enabling quick and precise opening and closing operations of the recloser.
Current Transformers and Voltage Transformers: Some reclosers are equipped with current transformers and voltage transformers to measure current and voltage signals in the line. These transformers provide data support for protective devices and control devices, enabling the monitoring and protection functions of the power system.