• Outdoor Ring Main Unit (RMU SF6)
  • Outdoor Ring Main Unit (RMU SF6)
  • Outdoor Ring Main Unit (RMU SF6)
Outdoor Ring Main Unit (RMU SF6)
discuss personally
Model
HXGN15-12
Basic info
Brand Wone
Model NO. Outdoor Ring Main Unit (RMU SF6)
Rated voltage 12kV
Series HXGN15
Product Detail

Product overview: 

  • HXGN15-12  Ring Main Unit (SF6 sulfur hexafluoride gas switchgear), box type AC metal closed switchgear.

  • Rated AC frequency 50Hz/ 60Hz, maximum working voltage to 12kV, maximum working current to 4000A.

  • High reliability of operation verification in more than 50 countries and regions around the world,Kuwait, UAE, Saudi Arabia, Iraq, Qatar, Tanzania, Zimbabwe, Ghana, South Africa, Kenya, Zambia, Libya, Myanmar, Philippines, Bangladesh, Nepal,Uzbekistan, Kazakhstan, Kyrgyzstan, Mongolia, Indonesia, Pakistan,Vietnam etc.

  • Mainly used in factories, workshops, residential areas, high-rise buildings and other places of power distribution system, ring network power supply, also suitable for box substation.

  • Meet many international standards: IEC62271-200:2003, GB3906, etc.

Product advantages:
 Leading technology:

  •  Standard anti-corrosion and salt spray environmental plan to meet the stringent environmental requirements of the site.

  •  The components can be equipped with ABB's original HAD/US type ISF6 circuit breaker or VD4-S type vacuum circuit breaker.

  •  SFL-12/24 switchgear with components assembled in China can also be used according to the needs of users.

  •  With perfect and reliable mechanical linkage, interlocking device, fully achieve the "five prevention" function (IP3X).

Cabinet put oneself in another's position:

  •  The whole is made of 2mm hot dip galvanized plate.

  •  Laser numerical control equipment cutting, drilling, bending, to ensure the processing accuracy.

  • The exterior is coated with electrostatic epoxy powder, which will not take off paint for 50 years.

Functional units:

  •  Manual and electric operation, remote control function.

  •  Load switch, combination electrical appliances, its installation mode is flexible, can be installed on the left and right side, front, flip.

  •  Two pressure relief holes, cable room and bus room (load switch) at the back of cabinet.

Busbar system:

  •  High quality three-phase tin bus copper bar, high mechanical strength, good heat dissipation.

 Processing and assembly:

  •  Dust-free workshop to ensure insulation.

  •  Assembly workers have been trained for at least 6 months.

  • Use power tools to ensure proper torque for bolting reinforcement.

  •  The copper bus is CNC cutting, punching and bending to ensure the accuracy.

  • Leybold Helium Mass Spectrometry Leak Detector, Germany -- ensure that the leakage rate of SF6 gas tank is below the national standard.

  •  Computer-controlled equipressure pumping and inflating integrated equipment for vacuum chamber -- to ensure no deformation of gas box and 99.9% purity of SF6 gas.

Product parameters:
Conditions of use:

  •  Altitude shall not exceed 2000m.

  •  Ambient air temperature not higher than +40 ° C, not lower than -5 ° C (average temperature within 24 hours not higher than +35 ° C).

  •  The humidity of the surrounding air should not exceed 50%. Low temperature allows a large relative temperature (e.g. +20 ° C is 90%). Consideration should be given to the effect of condensation caused by temperature changes.

  •  Inclination with vertical plane is not more than 5°, and the whole group of cabinets is relatively flat, in line with (GBJ232-2) standard.

  •  Requested in no violent vibration and impact, electrical components will not be corroded, no conductive dust place.

Ordering instructions:
The customer shall provide the following information:

  • Main loop scheme diagram, secondary loop system diagram and auxiliary circuit control mode.

  • Equipment layout and distribution room layout.

  • Brand and model of main electrical components of the equipment.

  • Incoming and outgoing lines.

  • Other special requirements can be negotiated with WONE Electric.

What are the structural characteristics of the RMU SF6?

Fully Sealed and Fully Insulated:

  • SF6 gas has excellent insulating properties. The ring main unit (RMU) uses SF6 gas for common box insulation, with all switching components sealed within the main enclosure. This design effectively prevents external environmental factors such as condensation, contamination, and flooding from affecting the internal electrical components, ensuring safe and reliable operation. The protection level typically reaches IP67.

Compact and Space-Efficient:

  • The design is compact, requiring a small footprint, allowing it to be installed in limited spaces. It is suitable for various outdoor locations, such as city streets, residential areas, and industrial parks, effectively saving space resources.

Corrosion-Resistant Design:

  • The enclosure is typically designed with special anti-corrosion features and painted with a protective coating, providing good resistance to corrosion. This allows the equipment to withstand harsh environmental conditions such as acid rain and salt fog, extending its service life.



Know your supplier
Wone
Main Categories
High voltage/Low voltage/Wire cable/Instrument meters/New energy/Tester/Production equipment/Generator/Electrical fittings/Integrated Electrical Equipment
Business Type
Design/Manufacture/Sales
Highest Annual Export (USD)
$50,000,000
Professional Experience
1 years
Workplace
65666m²m²
占位
占位
Related Knowledges
Application of Pre-integrated Prefabricated Substations in Renewable Energy Sector
Application of Pre-integrated Prefabricated Substations in Renewable Energy Sector
Against the backdrop of profound changes in the global energy landscape and the booming development of the new energy industry, the construction mode of traditional substations struggles to meet the rapid deployment needs of new energy projects. The modular intelligent prefabricated cabin substation, leveraging its innovative advantages, has become a key direction for optimizing the new energy power system. In - depth exploration of its technical principles, industry adaptability, and applicatio
Echo
06/13/2025
Research on Reliability Enhancement Scheme Implementation for Modular Intelligent Prefabricated Substations
Research on Reliability Enhancement Scheme Implementation for Modular Intelligent Prefabricated Substations
1 Implementation Strategies for the Scheme1.1 Deepen Survey and ResearchBefore constructing prefabricated cabin - type substations, it is necessary to conduct detailed surveys of local working conditions, clarify the construction scale and objectives, evaluate existing power facilities, plan projects, make up for infrastructure shortcomings, and adjust the construction rhythm. Meanwhile, control costs to avoid project suspension.1.2 Strengthen Structural ConstructionDuring promotion, multi - dim
Echo
06/13/2025
Comparative Analysis of 500 kV Prefabricated Substations vs. Conventional Substations
Comparative Analysis of 500 kV Prefabricated Substations vs. Conventional Substations
The secondary equipment area of conventional substations uses reinforced concrete or prefabricated steel structures, facing issues like long construction cycles, unreasonable functional zone design, strict environmental assessments, dust, noise, and disturbances. Primary and secondary equipment can only be installed after civil works and decoration, lowering construction efficiency.Prefabricated cabin substations integrate modularity, intelligence, and cost - effectiveness, boasting green, energ
Dyson
06/13/2025
Operational Analysis of Prefabricated Enclosure Substations in Extreme Cold Climate Applications
Operational Analysis of Prefabricated Enclosure Substations in Extreme Cold Climate Applications
Under global climate diversity, alpine power construction faces technical and environmental challenges. Extreme climates, complex geology, and long - term low winter temperatures, along with ice, snow, and storms, strain electrical equipment stability and power facility construction (schedule, cost, maintenance). Traditional on - site substations, with long construction and poor adaptability, can’t meet alpine regions’ fast, stable power needs.Prefabricated cabin substations, as modu
Echo
06/13/2025
Implementation of Precast Foundations for Ring-Main Unit Compact Substations in Grid Modernization Initiatives
Implementation of Precast Foundations for Ring-Main Unit Compact Substations in Grid Modernization Initiatives
Compact substation boxes, with advantages like safe operation, high reliability, and easy maintenance, are used in urban grid construction/renovation. Structurally divided into American - style (high - cost, noisy, low - efficiency, gradually phased out) and European - style (large - sized but more advantages, still popular).To address their pros/cons, ring - network prefabricated ones were developed.I. Basic Materials for Prefabricated Compact Substation BoxesMaterials need hardness, strength,
Echo
06/13/2025
The design of the three-purpose grounding transformer
The design of the three-purpose grounding transformer
Underground Power Cable Transmission LinesDirect - buried power cable lines have large ground - distributed capacitance, causing high single - phase - to - ground short - circuit capacitive current. For 10 kV lines, if this current exceeds 10 A, arcs hardly self - extinguish, risking arc overvoltage and endangering line equipment. Arc extinction is thus necessary. With a Dyn - connected main transformer, an arc - suppression coil on the secondary neutral point suffices. For Yd - connected ones,
Dyson
06/12/2025
×
Inquiry
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!
商品视频播放