• 17.5 kV indoor  vacuum circuit breaker Evolution that Empowers
17.5 kV indoor vacuum circuit breaker Evolution that Empowers
discuss personally
Model
VD4 evo-17.5-1250
Basic info
Brand ABB
Model NO. 17.5 kV indoor vacuum circuit breaker Evolution that Empowers
Rated voltage 17.5kV
Rated normal current 1250A
Rated frequency 50/60Hz
Series VD4 evo
Product Detail

Description:

VD4 evo circuit breakers are used in power distribution systems for controlling and protecting cables, transformer and distribution substations, motors, transformers and capacitor banks. VD4 evo includes a range of sensors for a seamless transition from traditional to digitally connected medium voltage circuit breakers. The integrated sensors enable advanced monitoring and diagnostic features for real-time monitoring of thermal, mechanical, and electrical parameters, allowing remote asset management and thus reducing maintenance cost and contributing to reduced downtime.
VD4 evo is also available in standard configurations without sensors. The flexibility of the design enables future digital upgrades, including sensors, if required.

Features:

  • Full monitoring and diagnostics (M&D) flexibility.
  • Mechanical chain and accessories anomalies detection.
  • Loose connections detection and circuit breaker contacts monitoring.
  • Advanced thermal checks & electrical life.
  • The most compact medium voltage circuit breaker selection for your application.
  • Third-party verified Environmental Product Declaration (EPD) for transparency of the environmental impact of the circuit breaker.
  • QR code for fast retrieval of online documentation.
  • Intuitive dashboard based on the Web browser-based HMI.

 Technical Characteristics:

Scope:

  • Withdrawable and fixed medium voltage circuit breakers for primary distribution.
  • The digital evolution of the IEC indoor vacuum circuit breaker VD4.
  • VD4 evo p150 17.5 kV, up to 1250 A, 40 kA withdrawable (for UniGear ZS1 650 mm) and fixed.
  • More ratings to be released soon.

Benefits:

  • New intelligence reduces the risk of power outages by 30 percent and increases operation and maintenance efficiencies by as much as 60 percent.
  • Enables reduced operating expenses (OpEx) by reducing outages and maintenance cost.
  • The most compact 17 kV 40 kA breaker, enabling 15 percent of space saving.
  • VD4 evo can be directly integrated with ABB’s ZEE600 SCADA solution enabling a direct cloud connection, or alternatively integrated with a third-party SCADA and gateway.
Know your supplier
ABB
As an authorized distributor of ABB products, we take great pride in our partnership.
Main Categories
High voltage/Low voltage
Business Type
Sales
Highest Annual Export (USD)
$580000000
Professional Experience
11 years
Workplace
20000m²
占位
占位
Documents
Public.
Evolution that Empowers
Manual English
PDF
FAQ
Q: What inspections should be performed after a short-circuit fault in a vacuum circuit breaker?
A: Check contact erosion: Minor erosion is acceptable (cumulative wear ≤3mm), but replace the vacuum interrupter if damage is severe. Test switching time and synchronization: Ensure values meet specifications to prevent operational issues caused by mechanism changes. Clean arc byproducts: Remove debris from the interrupter surface and inspect insulation components for impact damage or cracks.
Q: How to determine if a vacuum interrupter has failed?
A: Visual inspection: Check for cracks in the glass/ceramic housing or oxidation/discoloration of the internal shield. Vacuum degree detection: Use a high-frequency spark leak detector or professional vacuum degree tester. Replace the interrupter immediately if the vacuum degree decreases. Withstand voltage test: Perform a power frequency withstand voltage test at the rated voltage (e.g., 42kV/1min for 12kV products). Failure indicates the interrupter has failed.
Related Products
Related Knowledges
What aspects should be paid attention to when installing medium-voltage switch cabinets during the initial stage of subway operation?
What aspects should be paid attention to when installing medium-voltage switch cabinets during the initial stage of subway operation?
1. Statistics on Common Faults of Medium-Voltage Switchgear in the Early Operation StageAs project participants, we found during the early operation of a new metro line: 21 sets of power supply equipment were put into use, with a total of 266 accident phenomena in the first year. Among them, 77 faults occurred in medium-voltage switchgear, accounting for 28.9%—significantly higher than faults in other equipment. Statistical analysis shows that major fault types include: protection device s
Felix Spark
06/11/2025
Practice of Intelligent Switchgear Transformation in the 6kV Working Section of a Power Plant
Practice of Intelligent Switchgear Transformation in the 6kV Working Section of a Power Plant
Due to the long service life and severe aging of the equipment, the switches in the 6kV working section of Unit 6 of a certain power plant have potential safety hazards such as deformed locating pins, abnormal closing positions of the earthing switches, and malfunctions of the protection devices. These hazards have threatened the stable operation of the unit, making the transformation extremely urgent. Meanwhile, considering the recent cases of electric shock casualties involving medium-voltage
Echo
06/11/2025
Analysis of the Safety and Reliability Assurance of Medium-Voltage Switchgear
Analysis of the Safety and Reliability Assurance of Medium-Voltage Switchgear
As a professional engaged in power system operations, I recognize that medium-voltage (MV) switchgear plays a pivotal role in power distribution, metering, and protection. Ensuring its operational safety and reliability is critical—any malfunction can severely disrupt the entire power system. To enhance reliability, we must prioritize design-level optimizations, enabling MV switchgear to fulfill its functions and safeguard grid stability.1. Definition of Medium-Voltage SwitchgearIn my prac
Felix Spark
06/10/2025
What should be noted when using indoor vacuum circuit breakers?
What should be noted when using indoor vacuum circuit breakers?
I. Overvoltage PreventionVacuum circuit breakers excel in interrupting performance, but high overvoltage may occur across inductors during the switching of inductive loads due to abrupt changes in loop current, which requires special attention. When switching small-capacity motors, starting currents are large, so measures like step-down starting should be adopted to limit the current.Transformers with different structures show distinct characteristics: oil-immersed transformers have high impulse
Echo
06/10/2025
The application of indoor high-voltage vacuum circuit breakers
The application of indoor high-voltage vacuum circuit breakers
In the first half of 2007, as project participants from the Electromechanical Equipment Company of Huaibei Mining Group, we carried out a technical transformation of the 10kV substation in the East Factory Area. Our primary task was to replace the original 10kV disconnector - oil - immersed circuit breaker units with ZN20 indoor high - voltage vacuum circuit breakers.Previously, the SN10 - 10 oil - immersed circuit breakers had been in operation for an extended period, leading to severe oil leak
Echo
06/09/2025
What are the common faults and corresponding solutions for indoor drawer-type high-voltage vacuum circuit breakers?
What are the common faults and corresponding solutions for indoor drawer-type high-voltage vacuum circuit breakers?
Inability to Push In or Withdraw the Draw-out CarriageThe main manifestation is difficulty in inserting the carriage, which may cause equipment damage and threaten production when severe. The causes and countermeasures are shown in Table 1.The circuit - breaker fails to close. It manifests as the closing core actuating but the circuit - breaker not closing successfully; or the closing core not actuating, which shows that the control circuit of the circuit - breaker is open - circuited or the mec
Felix Spark
06/09/2025
×
Inquiry
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!
商品视频播放