• 12kV/24kV/36kV/40.5Kv Compact Substation
12kV/24kV/36kV/40.5Kv Compact Substation
discuss personally
Model
YBM-40.5/630
Basic info
Brand ROCKWILL
Model NO. 3.12kV /24kV/36kV/40.5Kv Compact Substation
Rated voltage 40.5kV
Rated normal current 630A
Rated frequency 50/60Hz
Series YBM
Product Detail

Descripton

The YBM series products represent a highly integrated power distribution solution, meticulously assembling medium-voltage (MV) switchgear, transformers, and low-voltage (LV) distribution equipment based on fixed connection schemes. Engineered for versatility, this series of substations is ideally suited for diverse applications, including neighborhood utility units, hotels, large-scale construction sites, and high-rise buildings. It operates efficiently within voltage ranges of 12kV, 24kV, 36kV, and 40.5kV, at a frequency of 50Hz, and can handle capacities of up to 2500kVA.

Adhering to stringent international standards, the YBW series complies with IEC60076 and IEC1330, as well as the ANSI/IEEE standards C57.12.00, C57.12.20, and C57.12.90. Additionally, it meets the requirements of BS171 and SABS 780, ensuring reliable performance and quality assurance across various regions and industries.

Structure Characteristics

  • Our box type transformer substations come in two distinct configurations: corridor - style and non - corridor - style. The frames are constructed from high - quality anti - corrosive steel through welding, while the bases are made of hot - galvanized steel.

  • Each box - type transformer substation consists of three compartments: the high - voltage (HV) cabinet, the low - voltage (LV) cabinet, and the transformer cabinet. The internal layout can be tailored to specific customer needs. The double - layer roof design features an air - filled cavity, which provides effective insulation against temperature increases.

  • These substations rely on natural air cooling as the standard option. However, forced air cooling and automatic anti - condensation equipment can be added as optional enhancements. To safeguard the transformer, various combinations of load switches and fuses are available.

  • They support multiple power supply modes, including terminal power supply, ring power supply, and dual power supply. The LV cabinets have a welded structure and are equipped with screen - type nameplates. Additionally, the cabinets are firmly fastened to the tank for stability.

Main Technical Specifications

Service Condition

  • Both indoor or outdoor

  • Air temperature: 

  • Maximum temperature: +40℃; Minimum temperature:-25℃

  • Humidity: Monthly average humidity 95%; Daily average humidity 90% .

  • Altitude above sea level: Maximum installation altitude: 2000m.

  • Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.

  • No frequent violent shake

Note: Beyond those services condition should enquiry to manufacturer technical dept during order

Note: The above parameter is only subject to our standard design, special requirement can be customized


Know your supplier
ROCKWILL
Rockwill Electric Group Global Manufacturer of High voltage and medium-voltage power equipment and smart grid solutions. Headquartered in Wenzhou, China. Serving 100+ countries with quality, innovation, and trust. What We Offer: • HV-MV switchgear (VCB, SF₆ circuit breakers, RMU, GIS) • Distribution transformers and substations • Smart grid and monitoring systems • Solar, wind, EV charging, and energy storage solutions • EPC turnkey power projects Certified: ISO 9001 / ISO 14001 / ISO 45001
Main Categories
High voltage
Business Type
Design/Manufacture/Sales
Highest Annual Export (USD)
$150,000,000
Professional Experience
16 years
Workplace
108000m²m²
占位
占位
Related Products
Related Knowledges
Installation and Commissioning of 10kV Dry-Type Transformers
Installation and Commissioning of 10kV Dry-Type Transformers
By James, 10 Years of Electrical Equipment Maintenance ExperienceHi everyone, I’m James, and I’ve been working in electrical equipment fault repair for 10 years.Over the past decade, I’ve worked in factories, substations, and distribution rooms of all sizes, involved in the installation, commissioning, maintenance, and troubleshooting of dry-type transformers. Dry-type transformers are among the most common electrical devices we deal with on a daily basis.Today, a new colleague
James
07/01/2025
What are the reasons for low insulation at the low-voltage side of a dry-type transformer?
What are the reasons for low insulation at the low-voltage side of a dry-type transformer?
Hi everyone, I’m Felix, and I’ve been working in electrical equipment fault repair for 15 years.Over these years, I’ve traveled across factories, substations, and distribution rooms all over the country, troubleshooting and repairing all kinds of electrical equipment. Dry-type transformers are among the most common devices we deal with.Today, a friend asked me:“What does it mean when the low-voltage side of a dry-type transformer has low insulation resistance?”Great
Felix Spark
07/01/2025
What tests are required for dry-type transformers?
What tests are required for dry-type transformers?
1 Pre - commissioning InspectionAs a front - line tester, before formally commissioning a dry - type transformer, I need to carry out a comprehensive and systematic inspection. First, I conduct a visual inspection of the transformer body and its accessories, carefully checking for mechanical damage or deformation. Then, I check whether the leads of the high - and low - voltage windings are firmly connected and whether the bolt tightening torque meets the standard requirements (usually 40 - 60N&m
Oliver Watts
07/01/2025
What aspects need attention during the installation of dry-type transformers?
What aspects need attention during the installation of dry-type transformers?
1 Pre - installation PreparationAs a front - line installer, I know very well that the preparation work before installing a dry - type transformer must be thorough. First, I will carefully review the design drawings and technical documents, and check one by one the technical parameters such as the model specification, rated capacity, and voltage level of the transformer to ensure they are in full compliance with the design requirements. Then, I will conduct an unpacking inspection of the transfo
James
07/01/2025
What are the causes of dry-type transformers burning out during operation?
What are the causes of dry-type transformers burning out during operation?
1 Fault PhenomenonI am engaged in front - line fault maintenance work, and recently encountered problems with dry - type transformers. Dry - type transformers have a simple structure, are convenient for transportation, and easy for maintenance. They are widely used in power distribution places with relatively high environmental protection requirements. Because of their good fire - resistance, they can be installed in load - center areas to reduce voltage loss and power loss.The property manageme
Felix Spark
07/01/2025
Method for Automatic Isolation of Customer Equipment Faults by Load Switches in Distribution Networks
Method for Automatic Isolation of Customer Equipment Faults by Load Switches in Distribution Networks
1 OverviewDistribution network safety has long been under - addressed, with its automation lagging substation automation . Using 10 kV intervals of existing substations to set line section points meets future grid needs . Configuration of distribution switches, section switches, and protection must match substation outgoing - line protection for reliability. Fault isolation, self - healing, and restoration are key to distribution automation .Scholars have studied smart distribution network fault
Felix Spark
06/30/2025
×
Inquiry
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!