Medium Voltage Switchgear

Electrical4u
03/25/2024 09:48:15

Medium Voltage Switchgear

From 3 KV to 36 KV switchgear system is categorized as medium voltage switchgear or MV switchgear. These switchgears are of many types. They may metal enclosed indoor type switchgear, metal enclosed outdoor type switchgear, outdoor type switchgear without metal enclosure, etc. The interruption medium of this switchgear may be insulating oil, SF6 gas or vacuum. The main requirement of power network is to interrupt current during faulty condition irrespective of what type of CB is used in the MV switchgear system. Although it may be capable of functioning in other conditions also.
Medium voltage switchgear, should be capable of,

  1. Normal ON/OFF switching operation.

  2. Short circuit current interruption.

  3. Switching of capacitive currents.

  4. Switching of inductive currents.

  5. Some special application.

All the above-mentioned functions must be carried out with a high degree of safety and reliability.

Short Circuit Current Interruption

The main focus of circuit breaker design is to that all circuit breakers should be capable of interrupting short circuit current with a high degree of reliability and safety. The number of faulty tripping occurred during the total lifespan of a circuit breaker mainly depends upon the location of the system, the quality of the system and environment conditions. If the number of tripping is much high, the best choice is vacuum circuit breaker as it may not require any maintenance up to 100 faulty tripping with short circuit current up to 25 KA. Whereas, other circuit breakers require maintenance after 15 to 20 faulty tripping with same short circuit current of CB. The substations reunited in rural areas are generally of an outdoor type, and most of them are the unattended type. Hence for this type of applications maintenance free outdoor type, medium voltage switchgear is most suitable. Porcelain clad vacuum circuit breaker meets this demand against the conventional indoor kiosks.

Switching of Capacitive Current

The capacitor bank is used in medium voltage power system to improve power factor of the system. Unloaded cable and unloaded overhead lines has also capacitive charging current. The capacitor bank and unloaded power lines should be disconnected from the system safely without re-ionization. Re-ionization in the contact gap causes over voltage in the system. Vacuum circuit breaker meets the requirement.
Medium Voltage Switchgear
While switching on a capacitor bank, a high rate of rise of making current will flow through the CB contacts. Circuit breaker with liquid quenching medium and tulip contacts may suffer from contact pin retardation. Vacuum medium voltage switchgear is most perfect choice for this purpose, as vacuum circuit breaker has low electric arcing during short pre arcing time.

Switching of Inductive Current

Older VCB had current chopping level of 20 A when these breakers were used to switch transformers, special surge protection device were required. Modern VCB has very low chopping current which is about 2 – 4A. Hence modern vacuum medium voltage switchgear is very much suitable for switching an unloaded transformer. As the modern VCB chops the current at a very low level, there is no need of additional surge protection devices. Hence VCB is suitable for very low inductive load switching. But when the inductive current in the system is low but not very low VCB is the best choice.

Special Application of Medium Voltage Switchgear

Arc Furnace

An electric arc furnace is required to be switched OFF and ON frequently. The current to be switched may be from 0 to 8 times of the rated current of the furnace. An electric arc furnace is to be switched ON and OFF at its normal rated current up to 2000A, around 100 times per day. A normal, SF6 circuit breaker, air circuit breaker and oil circuit breaker is not at all economical for this frequent operation. Standard vacuum circuit breaker is most suitable alternative for this frequent high current circuit breaker operation.

Railway Traction

Another application of medium voltage switchgear is single phase railway track system. The main function of the circuit breaker associated with railway traction system is to interrupt short circuit, on the overhead catenary system which occurs frequently and it is transient. Hence, a circuit breaker used for this purpose should have, short breaking time for small contact gap, short arcing time, quick breaking, and VCB is the best possible solution. Arcing energy is much higher in the single-phase CB than 3 phase CB. It is still much lower in a vacuum circuit breaker than that in a conventional circuit breaker. The number of short circuits occurs in the overhead catenary system is much higher than those occurring on electrical transmission system. Medium voltage switchgear with vacuum circuit breaker is most suitable for traction application. We can conclude that, in the medium voltage system where the tripping rate is very high, MV Vacuum Switchgear is the most suitable solution.