High Voltage Air-Break Disconnectors and Earthing Switches: Function, Types, and Routine Testing
Function of High Voltage Air-Break Disconnectors
High voltage air-break disconnectors play a critical role in high voltage power systems by providing electrical and visible isolation between different parts of the system. This isolation is essential for both normal day-to-day operations and maintenance or repair activities. The two primary forms of isolation are:
Types of High Voltage Air-Break Disconnectors and Earthing Switches
High voltage air-break disconnectors and earthing switches come in various types and mounting arrangements. The four most commonly used types are:
Routine Testing of High Voltage Disconnectors and Earthing Switches
Routine testing is performed to ensure that high voltage disconnectors and earthing switches meet the required standards and specifications. These tests are designed to reveal any faults in materials or construction without impairing the properties or reliability of the equipment. According to IEC 62271-1 and IEC 62271-102 standards, the following routine testing items are typically conducted:
Dielectric Test on the Main Circuit:A dry, short-duration power-frequency test with a frequency of 50 or 60 Hz is applied to the main circuit. The test voltage is specified in the relevant IEC standards and should be adjusted based on the altitude factor.
The purpose of this test is to verify the insulation strength of the disconnector and ensure that it can withstand the rated voltage without breakdown. The test voltage values are provided in the standard tables, and the altitude factor must be considered to account for the reduced dielectric strength of air at higher altitudes.
Importance of Routine Testing
Routine testing is essential to ensure that high voltage disconnectors and earthing switches are functioning correctly and can safely perform their isolation duties. These tests are typically conducted at the manufacturer's facility, but by agreement, they can also be performed on-site. The tests help identify any defects or weaknesses in the equipment before it is installed or put into service, ensuring that the power system operates reliably and safely.
By adhering to the IEC 62271-1 and IEC 62271-102 standards, manufacturers and operators can maintain the integrity and performance of high voltage disconnectors and earthing switches, thereby enhancing the overall safety and efficiency of the power system.
When the insulation of disconnector and earth switch is provided only by solid-core insulators and air at ambient pressure, the power-frequency voltage withstand test may be omitted if the dimensions between the conductive parts – between phases, across open switching devices and between conductive parts and the frame – are checked by dimensional measurements.
Dielectric Testing of Earthing Switches and Auxiliary/Control Circuits in High Voltage Disconnectors
When performing a dielectric test on earthing switches, the test voltage is applied with the earthing switch in the open position. The test is conducted under two specific conditions to ensure proper insulation between different parts of the switch:
Between Adjacent Insulated Terminals (with Bases Earthed):The test voltage is applied between adjacent insulated terminals while the bases of the switch are earthed. This ensures that there is sufficient insulation between the terminals to prevent any accidental short circuits or electrical breakdown.
Between All Insulated Terminals Connected Together (with Bases Earthed):In this condition, all the insulated terminals are connected together, and the test voltage is applied between this group of terminals and the earthed bases. This test checks the overall insulation integrity of the switch, ensuring that there is no leakage current between the terminals and ground.
2. Dielectric Test on Auxiliary and Control Circuits in Operating Mechanism
Inspection and Verification of Conformity
Functional Tests
Dielectric Tests on Auxiliary and Control Circuits
Power Frequency Tests:Only power frequency tests are performed on the auxiliary and control circuits. The test voltage is either 1 kV or 2 kV with a duration of 1 second at a frequency of 50 or 60 Hz. This test ensures that the insulation of the low-voltage circuits can withstand the rated voltage without breakdown.
3. Measurement of the Resistance of the Main Circuit
For the routine test, the DC voltage drop or resistance of each pole of the main circuit is measured under conditions as similar as possible to those used during the type test. Specifically:The ambient air temperature and points of measurement should be as close as possible to those during the type test.
The measured resistance should not exceed 1.2 × Ru, where Ru is the resistance measured before the temperature-rise test. This ensures that the resistance of the main circuit remains within acceptable limits, indicating that the contacts are in good condition and the circuit can carry the rated current without excessive heating.
4. Design and Visual Checks
The disconnector and earthing switches must undergo thorough design and visual inspections to ensure they comply with the purchase specification. This includes:
5. Mechanical Operating Tests
Mechanical operating tests are conducted to ensure that the disconnectors or earthing switches function correctly within the specified voltage and supply pressure limits of their operating mechanisms. These tests are performed without voltage on or current flowing through the main circuit. The following aspects are verified:
Operating Mechanism Performance
Operating Cycles
The following operating cycles are performed to test the reliability and endurance of the disconnector or earthing switch:
During these operating cycles, the following characteristics are recorded or evaluated:
Auxiliary Contacts and Position Indicating Devices
The satisfactory operation of auxiliary contacts and position indicating devices (if any) is verified. These components provide critical feedback to the control systems and must function reliably to ensure proper system operation.
Post-Test Inspection
After completing the mechanical operating tests, no parts of the disconnector or earthing switch should be damaged. The device should remain in good working condition, with no signs of wear, deformation, or malfunction.
Main Circuit Resistance Measurement
The resistance of the main circuit is measured both before and after the mechanical endurance test. The resistance should not vary by more than 20% from the value measured before the test. This ensures that the contacts have not deteriorated or become misaligned during the testing process, which could affect the electrical performance of the device.
Special Considerations for High-Voltage Equipment
For disconnectors and earthing switches with a rated voltage of 52 kV and above, the mechanical operating routine tests may be performed on sub-assemblies. This allows for more manageable testing procedures while still ensuring that the overall performance of the device meets the required standards.
Conclusion
By conducting these comprehensive design and visual checks, as well as mechanical operating tests, manufacturers and operators can ensure that high-voltage disconnectors and earthing switches are reliable, safe, and capable of performing their intended functions under various operating conditions. These tests help identify any potential issues early in the process, ensuring that the equipment is ready for installation and service in high-voltage power systems.