This device is capable of monitoring and detecting various parameters according to the specifications outlined:
SF6 Gas Monitoring:
- Utilizes a specialized sensor for measuring SF6 gas density.
- Capabilities include measuring gas temperature, monitoring SF6 leak rates, and calculating the optimal date for refilling.
Mechanical Operation Analysis:
- Measures operational times for closing and opening cycles.
- Evaluates primary contacts separation speed, damping, and contact overtravel.
- Identifies signs of mechanical deterioration, such as increased friction, corrosion, breakage, spring fatigue, wear on linkage rods, and damping issues.
Recharging Motor Performance:
- Monitors motor supply voltage, current, and consumed energy.
- Detects defects in motors or limit switches and measures spring travel.
Hydraulic Operating Mechanism:
- Tracks pump motor operating time.
- Identifies internal and external leaks and monitors threshold pressure within the hydraulic system.
Switching Operations:
- Measures current during breaking operations.
- Assesses primary contact wear and arc duration.
Auxiliary and Control Circuits:
- Checks the continuity of operating coils, measures coil current, voltage, resistance, and armature operation time and energy consumption.
- Monitors auxiliary supply voltage and ensures heater integrity.