Dielectric combined voltage tests (BIAS test) on circuit breakers

Edwiin
12/25/2024

Dielectric Bias Testing of High-Voltage Circuit Breakers

Dielectric bias testing is a critical procedure used to evaluate the insulation performance of high-voltage circuit breakers (CBs) under conditions that simulate real-world voltage stresses. In this test, the circuit breaker is subjected to two separate voltages simultaneously: a power frequency (PF) voltage and either a switching (SW) impulse or a lightning impulse (LI). This combination of voltages mimics the actual voltage conditions that an open circuit breaker may experience during operation.

Test Setup and Conditions

  1. Power Frequency (PF) Voltage:

    • Applied at one terminal (Terminal A).
    • For SW bias tests, the PF voltage corresponds to the rated phase-to-ground voltage of the system. This reflects real-world conditions where switching overvoltages often occur near the peak of the power frequency voltage wave.
    • For LI bias tests, the PF voltage is set to 70% of the rated phase-to-ground voltage. This is because lightning overvoltages can occur at any point in time, and the standard has chosen a compromise between the least and most severe stress conditions.
  2. Impulse Voltage (SW or LI):

    • Applied at the other terminal (Terminal B).
    • The impulse voltage is synchronized to coincide with the opposite peak of the power frequency voltage. This means that if the PF voltage is at its negative peak, the impulse voltage will be applied at its positive peak, and vice versa.
    • The total voltage between the terminals is the sum of the PF voltage and the impulse voltage.

Synchronization

  • For SW bias tests, the switching impulse is synchronized with the maximum value of the negative PF voltage. This ensures that the circuit breaker is tested under the most severe conditions, as switching overvoltages typically occur when the power frequency voltage is near its peak.
  • For LI bias tests, the lightning impulse is also synchronized with the negative peak of the PF voltage, but the PF voltage is lower (70% of the rated voltage) due to the random nature of lightning strikes.

Purpose of the Test

The purpose of dielectric bias testing is to ensure that the circuit breaker's insulation system can withstand the combined effects of power frequency and impulse voltages, which are common in real-world applications. By subjecting the CB to these conditions, manufacturers can verify that the insulation will not break down under the most challenging voltage scenarios.

Example: ABB High-Voltage Circuit Breaker in Dielectric Bias Test

In the following scenario, an ABB high-voltage circuit breaker is being tested under dielectric bias conditions:

  • Terminal A: Power frequency (PF) voltage is applied.
  • Terminal B: Either a switching (SW) or lightning (LI) impulse is applied, synchronized with the maximum value of the negative PF voltage.

This setup ensures that the circuit breaker is tested under conditions that closely resemble those it would encounter in actual operation, providing a reliable assessment of its insulation performance.

Key Points Summary

  • PF Voltage: Applied at one terminal, corresponding to the rated phase-to-ground voltage for SW bias tests or 70% of the rated voltage for LI bias tests.
  • Impulse Voltage: Applied at the other terminal, synchronized with the opposite peak of the PF voltage.
  • Total Voltage: The sum of the PF voltage and the impulse voltage.
  • Synchronization: For SW bias tests, the impulse is synchronized with the maximum negative PF voltage; for LI bias tests, the same synchronization is used, but with a lower PF voltage.
  • Purpose: To simulate real-world voltage conditions and ensure the circuit breaker's insulation can handle the combined stresses of power frequency and impulse voltages.
Edwiin

Online condition monitoring device (OLM2) on high voltage Circuit Breakers
Online condition monitoring device (OLM2) on high voltage Circuit Breakers
This device is capable of monitoring and detecting various parameters according to the specifications outlined:SF6 Gas Monitoring:Utilizes a specialized sensor for measuring SF6 gas density.Capabilities include measuring gas temperature, monitoring SF6 leak rates, and calculating the optimal date for refilling.Mechanical Operation Analysis:Measures operational times for closing and opening cycles.Evaluates primary contacts separation speed, damping, and contact overtravel.Identifies signs of mec
Edwiin
02/13/2025
Anti pumping function in circuit breakers operating mechanism
Anti pumping function in circuit breakers operating mechanism
The anti - pumping function stands as a crucial characteristic of control circuits. In the absence of this anti - pumping function, assume that a user connects a maintained contact within the closing circuit. When the circuit breaker is closed onto a fault current, the protective relays will promptly trigger a tripping action. However, the maintained contact in the closing circuit will attempt to close the breaker (once again) onto the fault. This repetitive and dangerous process is referred to
Edwiin
02/12/2025
Ageing phenomena of current pass blades in high voltage disconnector switch
Ageing phenomena of current pass blades in high voltage disconnector switch
This failure mode has three primary origins:Electrical Causes: The switching of currents, such as loop currents, can lead to localized wear. At higher currents, an electric arc may burn at a specific spot, increasing the local resistance. As more switching operations occur, the contact surface wears down further, causing an increase in resistance.Mechanical Causes: Vibrations, often due to wind, are the main contributors to mechanical aging. These vibrations cause abrasion over time, leading to
Edwiin
02/11/2025
Initial Transient Recovery Voltage (ITRV) for high voltage circuit breakers
Initial Transient Recovery Voltage (ITRV) for high voltage circuit breakers
Transient Recovery Voltage (TRV) stress similar to that encountered during a short-line fault can also occur due to the busbar connections on the supply side of a circuit breaker. This specific TRV stress is known as Initial Transient Recovery Voltage (ITRV). Given the relatively short distances involved, the time to reach the first peak of ITRV is typically less than 1 microsecond. The surge impedance of the busbars within a substation is generally lower compared to that of overhead lines.The f
Edwiin
02/08/2025
Inquiry
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!