What Is A Shunt Reactor

What is Shunt Reactor

A shunt reactor is a piece of electrical equipment used in high voltage power transmission systems to stabilize the voltage during load variations. A traditional shunt reactor has a fixed rating and is either connected to the transmission line all the time or switched in and out depending on the load.

A three phase shunt reactor is generally connected to 400KV or above electrical bus system for capacitive reactive power compensation of the power system and to control dynamic over voltage occurring in the system due to load rejection.

The shunt reactor should be capable of withstanding maximum continuous operating voltage (5% higher the rated voltage in case of 400 KV system) under normal power frequency variation without exceeding the top spot temperature of 150oC at any part of the shunt reactor.

The shunt reactor should be of gapped core type or magnetically shielded air core type. Both of these designs help to maintain the impedance of the reactor fixed. The impedance should be maintained at a constant value for avoiding harmonic current generated due to the system over voltage.
shunt reactor
The shunt reactor has mainly core losses during its normal operating condition. So, care should be taken for minimizing the core losses during design.

Measurement of Losses in Shunt Reactor

We should measure the losses of a shunt reactor at rated voltage and frequency. But for very high voltage shunt reactor, it may be difficult to arrange such a high test voltage during measurement of losses. This difficulty can be overcome, by measuring the losses of the shunt reactor at any voltage lower than the system voltage of the reactor. Then this measured loss is multiplied by the square of the ratio of rated current to the current of the reactor at applied reduced test voltage to obtain the loss at rated voltage.


As the power factor of the shunt reactor is very low, loss measurement of shunt reactor by conventional wattmeter is not very reliable, instead of bridge method of measurement may be adopted for better accuracy.
This test can not segregate the losses in various parts of the reactor. To avoid, correction of test result for a reference temperature, it is preferable to take the measurement when the average temperature of the winding becomes equal to the reference temperature.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Electrical4u

Electrical4U is dedicated to the teaching and sharing of all things related to electrical and electronics engineering.

Classification of Electric Power Distribution Network Systems
Classification of Electric Power Distribution Network Systems
The typical electric power system network is categorized into three main components: generation, transmission, and distribution. Electric power is produced in power plants, which are often located far from load centers. As a result, transmission lines are employed to deliver power over long distances.To minimize transmission losses, high-voltage power is used in transmission lines, and the voltage is reduced at the load center. The distribution system then delivers this power to end-users.Types
Edwiin
06/05/2025
Why is the Ground Wire Always Positioned Above the Overhead Power Lines?
Why is the Ground Wire Always Positioned Above the Overhead Power Lines?
Ground Wire in Overhead Transmission LinesThe ground wire (also called earth wire or OPGW) installed above phase lines in overhead transmission lines acts as a key protective and safety component. It provides lightning protection, ground fault defense, and helps prevent electrical system disruptions.In overhead transmission lines, positioning the ground wire above phase lines serves specific safety and performance purposes. Referred to as a "shield wire" or "static wire," this configuration has
Edwiin
06/04/2025
What is the Power Angle in a Power Transmission Line?
What is the Power Angle in a Power Transmission Line?
The power angle, denoted by δ, is the phase angle difference between two voltage levels in a power transmission line. Specifically, it represents the angular discrepancy between the sending-end voltage phasor and the receiving-end voltage (or between voltages at two bus points). In simpler terms, it quantifies the phase shift between voltage and current waveforms in the transmission line.Also referred to as the torque angle or load angle, this parameter is critical for two key reasons: it
Edwiin
06/04/2025
Permanent Magnet Moving Coil or PMMC Instrument
Permanent Magnet Moving Coil or PMMC Instrument
DefinitionInstruments that utilize a permanent magnet to generate a stationary magnetic field within which a coil moves are known as Permanent Magnet Moving Coil (PMMC) instruments. They operate on the principle that torque is exerted on a moving coil situated in the magnetic field of a permanent magnet. PMMC instruments provide accurate results for direct current (DC) measurements.Construction of PMMC InstrumentThe moving coil and the permanent magnet are the key components of a PMMC instrument
Edwiin
05/30/2025
Inquiry
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!