Measurement of Reactance of a Shunt Reactor

Electrical4u
03/25/2024

What Is The Measurement Of Reactance Of A Shunt Reactor

The following two factors to be considered during measurement of reactance of a shunt reactor.

  • The reactance of a shunt reactor is approximately equal to its impedance as the resistive component of the impedance in shunt reactor is negligible.

  • The V-I characteristics of the shunt reactor is almost linear under operating range of applied voltage. This is because, gapped core is used in the shunt reactor to prevent magnetic saturation of the core within normal operational range.

The simple formula of impedance in ohm is

Where, V is voltage in volt and I is current in ampere.

But in the case of shunt reactor, impedance Z = reactance X.
Hence, here

Where, V is applied voltage across the winding of the reactor and I is the corresponding current through it.
As the V-I characteristic of the reactor is linear, reactance of the reactor winding remains fixed for any applied
voltage below the maximum rated value.
In the case of reactance measurement of three phase shunt reactor, we use sinusoidal three phase supply voltage of power frequency (50 Hz) as test voltage. We connect three supply phases to three terminals of the reactor winding as shown. Before that we should make sure that the neutral terminal of the winding is properly earthed.

After switching on the supply, we measure the current flowing through each phase of the winding with the help of suitably sensitive clip on meter. After current measurements, we have to calculate the average current per phase. The average is taken as algebraic summation of three phase currents divided by 3. The measured reactance of the three phase shunt reactor is taken as

measurement of reactance of shunt reactor

For three phase reactors with magnetic iron path for zero sequence flux, zero sequence reactance may be measured as follows,
In that case the three terminals of the reactor are shorted and single phase supply is applied between common phase terminal and neutral terminal of the winding. After measuring the current through the common path we have to divide the applied single phase voltage by it. We then multiply 3 with the result to obtain zero sequence reactance per phase.

measurement of zero sequence reactance of shunt reactor

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Electrical4u

Electrical4U is dedicated to the teaching and sharing of all things related to electrical and electronics engineering.

Classification of Electric Power Distribution Network Systems
Classification of Electric Power Distribution Network Systems
The typical electric power system network is categorized into three main components: generation, transmission, and distribution. Electric power is produced in power plants, which are often located far from load centers. As a result, transmission lines are employed to deliver power over long distances.To minimize transmission losses, high-voltage power is used in transmission lines, and the voltage is reduced at the load center. The distribution system then delivers this power to end-users.Types
Edwiin
06/05/2025
Why is the Ground Wire Always Positioned Above the Overhead Power Lines?
Why is the Ground Wire Always Positioned Above the Overhead Power Lines?
Ground Wire in Overhead Transmission LinesThe ground wire (also called earth wire or OPGW) installed above phase lines in overhead transmission lines acts as a key protective and safety component. It provides lightning protection, ground fault defense, and helps prevent electrical system disruptions.In overhead transmission lines, positioning the ground wire above phase lines serves specific safety and performance purposes. Referred to as a "shield wire" or "static wire," this configuration has
Edwiin
06/04/2025
What is the Power Angle in a Power Transmission Line?
What is the Power Angle in a Power Transmission Line?
The power angle, denoted by δ, is the phase angle difference between two voltage levels in a power transmission line. Specifically, it represents the angular discrepancy between the sending-end voltage phasor and the receiving-end voltage (or between voltages at two bus points). In simpler terms, it quantifies the phase shift between voltage and current waveforms in the transmission line.Also referred to as the torque angle or load angle, this parameter is critical for two key reasons: it
Edwiin
06/04/2025
Permanent Magnet Moving Coil or PMMC Instrument
Permanent Magnet Moving Coil or PMMC Instrument
DefinitionInstruments that utilize a permanent magnet to generate a stationary magnetic field within which a coil moves are known as Permanent Magnet Moving Coil (PMMC) instruments. They operate on the principle that torque is exerted on a moving coil situated in the magnetic field of a permanent magnet. PMMC instruments provide accurate results for direct current (DC) measurements.Construction of PMMC InstrumentThe moving coil and the permanent magnet are the key components of a PMMC instrument
Edwiin
05/30/2025
Inquiry
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!