Motor Protection Relay for High Voltage Induction Motor

Electrical4u
03/26/2024

What Is A Motor Protection Relay

Above 90% of motors used in an industry are induction motors, because they are cheap, robust and easy to maintain. For higher HP (>250HP) motors we prefer high voltage, because it will reduce operating current and the size of the motor.

Why We Require Protection of Motors?

To understand this we need to know the cost associated with the failure of motor, i.e.

  • Loss of production (Cost of production)

  • Replacement of motor (Replacement cost)

  • Cost of repair

  • Cost of man hours due to this emergency

The basic function of a protective relay is to identify the fault and isolate faulty part from the healthy part of the system. This will improve the reliability of power system.
For protection of motor, we have to identify the various causes of failure and to address the same. The various causes of failure are as below

  • Thermal stress on winding

  • Single phasing

  • Earth fault

  • Short circuit

  • Locked rotor

  • Number of hot starts

  • Bearing failure

Brief descriptions of the different failures are given below:

  • Thermal Stress on Winding –
    If a motor runs continuously more than its rated capacity then this will over heat the winding and insulation. Subsequently deteriorate the winding insulation resulting in failure of motor. If the 
    voltage is less than the designed value then also it will over heat the winding at rated load and failure of the motor can occur.

  • Single Phasing –
    Loss of one phase supplied to the motor (in case of 
    3-phase motor) leads to single phasing. If we start the motor on load, then the motor will fail due to imbalance.

  • Earth Fault –
    If any part of winding comes in contact with the ground then we can say the motor is earthed. If we start the motor then it will lead to failure of motor.

  • Short Circuit –
    If there is a contact between two phases of a three phase winding or between the turns of a phase, and then this will be termed as short circuit.

  • Locked Rotor –
    If the driven equipment is in jammed condition or the motor shaft is jammed, then this is known as locked rotor. If we start the motor then it will fail.

  • Number of Hot Start –
    Each motor is designed to withstand a certain number of hot starts. Consider a motor is in running condition, if we stop the motor and immediately start the same, then this is called as a hot start. Depending upon the thermal curve of a motor we have to give certain time to bring down the temperature of winding.

  • Bearing Failure –
    If bearing fails then rubbing of rotor on stator will occur, resulting physical damage of insulation and winding. The bearing failure can be avoided by monitoring the bearing temperature. Bearing temperature detector (BTD) is used for monitoring and tripping of motor in case of abnormality.

All motor protection relays operate on the basis of current taken by the motor. Motor protection relay is used for high voltage area having the following features

  • Thermal overload protection

  • Short circuit protection

  • Single phasing protection

  • Earth fault protection

  • Locked rotor protection

  • Number of start protection

For setting of the relay we require the CT ratio and full load current of the motor. The setting of different element is listed below

  • Thermal over Load Element –
    To set this element we have to identify the % of Full load current on which the motor is running continuously.

  • Short circuit Element –
    The range available for this element is 1 to 5 times of starting current. Time delay is also available. We normally set it at 2 times of starting current with a time delay of 0.1 second.

  • Single Phasing Element –
    This element will operate, if there is an unbalance in current of three phases. It is also called as unbalance protection. The element is set for 1/3rd of starting current. If it tripped during starting, then the parameter will changed to 1/2 of starting current.

  • Earth Fault Protection –
    This element measures the neutral current of star connected CT secondary. The range available for this element is 0.02 to 2 times of CT primary current. Time delay is also available. We normally set at 0.1 times of CT primary current with a time delay of 0.2 seconds. If tripped during starting of motor, then the time setting can be raised to 0.5 sec.

  • Locked rotor protection –
    The range available for this element is 1 to 5 times of full load current. Time delay is also available. We normally set at 2 times of FLC (Full Load Current). The time delay will be more than the starting time of the motor. “Starting time means the time require by the motor to reach its full speed.”

  • Number of hot start protection –
    Here we will provide the number of start allowed in specified time duration. By this we will limit the number of hot starts given to the motor.

The schematic diagram to connect a motor protection relay is as below

Modern digital motor protection relays are having some extra features, i.e. protection against no load running of a motor and thermal protection.
In case of no load running, the relay senses the motor current. If it is less than the specified value then it will trip the motor. We can also connect the temperature probe to the relay, which will monitor the bearing and winding temperature and trip the motor if it exceeds the specified value of temperature.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Electrical4u

Electrical4U is dedicated to the teaching and sharing of all things related to electrical and electronics engineering.

Classification of Electric Power Distribution Network Systems
Classification of Electric Power Distribution Network Systems
The typical electric power system network is categorized into three main components: generation, transmission, and distribution. Electric power is produced in power plants, which are often located far from load centers. As a result, transmission lines are employed to deliver power over long distances.To minimize transmission losses, high-voltage power is used in transmission lines, and the voltage is reduced at the load center. The distribution system then delivers this power to end-users.Types
Edwiin
06/05/2025
Why is the Ground Wire Always Positioned Above the Overhead Power Lines?
Why is the Ground Wire Always Positioned Above the Overhead Power Lines?
Ground Wire in Overhead Transmission LinesThe ground wire (also called earth wire or OPGW) installed above phase lines in overhead transmission lines acts as a key protective and safety component. It provides lightning protection, ground fault defense, and helps prevent electrical system disruptions.In overhead transmission lines, positioning the ground wire above phase lines serves specific safety and performance purposes. Referred to as a "shield wire" or "static wire," this configuration has
Edwiin
06/04/2025
What is the Power Angle in a Power Transmission Line?
What is the Power Angle in a Power Transmission Line?
The power angle, denoted by δ, is the phase angle difference between two voltage levels in a power transmission line. Specifically, it represents the angular discrepancy between the sending-end voltage phasor and the receiving-end voltage (or between voltages at two bus points). In simpler terms, it quantifies the phase shift between voltage and current waveforms in the transmission line.Also referred to as the torque angle or load angle, this parameter is critical for two key reasons: it
Edwiin
06/04/2025
Permanent Magnet Moving Coil or PMMC Instrument
Permanent Magnet Moving Coil or PMMC Instrument
DefinitionInstruments that utilize a permanent magnet to generate a stationary magnetic field within which a coil moves are known as Permanent Magnet Moving Coil (PMMC) instruments. They operate on the principle that torque is exerted on a moving coil situated in the magnetic field of a permanent magnet. PMMC instruments provide accurate results for direct current (DC) measurements.Construction of PMMC InstrumentThe moving coil and the permanent magnet are the key components of a PMMC instrument
Edwiin
05/30/2025
Inquiry
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!