Differential Protection of Generator or Alternator

Electrical4u
03/26/2024

What Is Differential Protection

Any internal fault inside the stator winding is cleared by mainly differential protection scheme of the generator or alternator.
The
differential protection is provided in the generator by using longitudinal differential relay.
generator differential protection
Generally instantaneous attracted armature type relays are used for this purpose because all they have high speed operation and also they are free from being affected by any AC transient of the power circuit.

There are two sets of current transformers, one CT is connected to the line side of the generator and other is connected to the neutral side of the generator in each phase. It is needless to say that the characteristics of all current transformers installed against each phase must be matched. If there is any major mismatched in the current transformer’s characteristics of both sides of the generator, there may be high chance of malfunctioning of differential relay during the fault external to the stator winding and also may be during normal operating conditions of the generator. To ensure that the relay does not operate for the faults external to the operated zone of the protection scheme, a stabilizing resistor is fitted in series with the relay operating oil. It also ensures that if one set of CT has been saturated, there will be no possibility of malfunctioning of the differential relay.

generator differential protection
It is always preferable to use dedicated current transformers for differential protection purpose because common current transformers may cause unequal secondary loading for other functionalities imposed on them. It is also always preferable to use all current transformers for differential protection of generators or alternators should be of same characteristics. But practically there may be some difference in characteristics of the current transformers installed at line side to those installed in neutral side of the generator.

These mismatches cause spill current to flow through the relay operating coil. To avoid the effect of spill current, percentage biasing is introduced in differential relay.
differential protection of generator with percentage biasing
The percentage biased differential relay comprises two restraint coils and one operating coil per phase. In the relay, the torque produced by operating coil tends to close the relay contacts for instantaneous tripping of circuit breakers but at the same time the torque produced by the restraint coils prevents to close the relay contacts as restraint coils torque is directed opposite of the operating coil torque. Hence during through fault the differential relay would not be operated because the setting of the relay is increased by restraint coils and also it prevents malfunctioning of relay due to spill current. But during internal fault in the winding of the stator, the torque produced by restraint coils is ineffective and the relay closes its contact when setting current flows through the operating coil.
Differential current pickup setting/bias setting of the relay is adopted based on the maximum percentage of allowable mismatch adding some safety margin.
The spill current level for the relay is to just operate it; is experienced as a percentage of the through fault current causing it. This percentage is defined as bias setting of the relay.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Electrical4u

Electrical4U is dedicated to the teaching and sharing of all things related to electrical and electronics engineering.

Classification of Electric Power Distribution Network Systems
Classification of Electric Power Distribution Network Systems
The typical electric power system network is categorized into three main components: generation, transmission, and distribution. Electric power is produced in power plants, which are often located far from load centers. As a result, transmission lines are employed to deliver power over long distances.To minimize transmission losses, high-voltage power is used in transmission lines, and the voltage is reduced at the load center. The distribution system then delivers this power to end-users.Types
Edwiin
06/05/2025
Why is the Ground Wire Always Positioned Above the Overhead Power Lines?
Why is the Ground Wire Always Positioned Above the Overhead Power Lines?
Ground Wire in Overhead Transmission LinesThe ground wire (also called earth wire or OPGW) installed above phase lines in overhead transmission lines acts as a key protective and safety component. It provides lightning protection, ground fault defense, and helps prevent electrical system disruptions.In overhead transmission lines, positioning the ground wire above phase lines serves specific safety and performance purposes. Referred to as a "shield wire" or "static wire," this configuration has
Edwiin
06/04/2025
What is the Power Angle in a Power Transmission Line?
What is the Power Angle in a Power Transmission Line?
The power angle, denoted by δ, is the phase angle difference between two voltage levels in a power transmission line. Specifically, it represents the angular discrepancy between the sending-end voltage phasor and the receiving-end voltage (or between voltages at two bus points). In simpler terms, it quantifies the phase shift between voltage and current waveforms in the transmission line.Also referred to as the torque angle or load angle, this parameter is critical for two key reasons: it
Edwiin
06/04/2025
Permanent Magnet Moving Coil or PMMC Instrument
Permanent Magnet Moving Coil or PMMC Instrument
DefinitionInstruments that utilize a permanent magnet to generate a stationary magnetic field within which a coil moves are known as Permanent Magnet Moving Coil (PMMC) instruments. They operate on the principle that torque is exerted on a moving coil situated in the magnetic field of a permanent magnet. PMMC instruments provide accurate results for direct current (DC) measurements.Construction of PMMC InstrumentThe moving coil and the permanent magnet are the key components of a PMMC instrument
Edwiin
05/30/2025
Inquiry
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!