Steam Calculator: How To Calculate Steam Consumption

Electrical4u
03/21/2024

WechatIMG1858.jpeg

What is Steam Consumption in a Pipe?

Steam consumed and steam utilized at the point of application are not equal. Normally steam consumed or generated in a steam boiler is more than what is required for use at the point of application.


The difference in steam consumption and steam utilization is due to:


  • Steam condensation when it travels on its way to point of use mainly due to exposed surfaces.

  • Leakages (if any)

When steam condenses on the wall of an exposed/uninsulated steam pipe, it gives up its enthalpy of evaporation.

Proper utilization of steam helps in saving in the input cost of water and coal. Saving of each kg of steam is directly proportional to the saving of some percentage of water, coal and electricity.

Calculation of steam consumption in a pipe during the start-up operation and normal continuous operation is possible, and will be discussed in detail below.

Steam Consumption in Steam Mains

Steam consumption within the pipe system needs to be judiciously monitored and controlled. The rate of condensation of the steam in the steam piping network depends upon the type of load (i.e. warm-up load or running load).

The rate of condensation of steam needs to be taken into account for sizing the steam traps, and also in finalizing the boiler output.

What is Warm-Up Load ?

During the plant start-up after a long time or from cold, then the steam is required to heat the system uniformly to bring the system close to the normal working temperature of the system.

The ‘warm-up load’ is the steam load which is associated with the steam consumption during the start-up of the plant. This can be either from the cold shut down, or from start-up after a very long time.

The rate of condensation of steam during the warm-up period is maximum. The design of steam trap shall be based on this load.

A good practice is to warm-up the system very slowly for safety-reasons, pipes have the benefit of reduced thermal and mechanical stress. Thus results in the following benefits:

  • Eliminations of leaks

  • Lower-maintenance-costs

  • Longer life for the pipes

  • No water hammer.

What is Process Plant Running Load?

Process plant running load is the steam load which is related to the normal (full load) continuous load of the plant. The rate of condensation of steam during the full load running a load of the plant is minimum.




How to Warm-Up a System?

Uniform and slow system warm-up can be achieved by a small by-pass valve in parallel to the main line isolation valve.

The time required to warm up the pipe network decides the warm-up (bypass) valve size. This valve can be a manual or automatic type depending on the user/client.

It is always better to discourage the practice of using the main valve for warm-up instead of the bypass valve. Since the main valve is far bigger in size (designed for full flow requirement) and not appropriate to use for small flow during the warm-up period.

As shown in figure1 above, before the main valve/bypass valve separator is installed to ensure that steam passing through the valve should be dry to protect the valve wear and tear.

If we provide sufficient time for the warming-up, then it is possible to get the following benefits:

  • For minimizing the pipe stress

  • For operational safety

  • Reduce start-up loads on boiler

The steam flowrate required to bring a pipework system up to operating temperature is a function of:

  • Mass

  • Specific heat of the material

  • Temperature increase

  • Enthalpy of evaporation of steam or Enthalpy of saturated steam

  • Allowable time




Where:

  • ms: Mean rate of condensation of steam in kg/hr

  • W: Total weight of pipe plus flanges and fittings in kg

  • Ts: Steam temperature oC

  • Tamb: Ambient temperature

  • Cp: Specific heat of pipe material in kj/kgoC

  • hfg: Enthalpy of evaporation or saturated enthalpy at operating pressure in kj/kg

  • t: Time of warming-up in minutes

Note: Suppose if the warm-up/heating time of the system is increased to 12 minutes from 6 minutes, then the initial flow rate of the steam can easily be reduced to half. If the warm-up/heating time of the system is increased to say 24 minutes, then the initial steam flow rate for heating can be reduced further.

Method to calculate the warm-up condensing load for a period of 30 minutes in a steam system

Let:

  • The system consists of carbon steel pipe of size — 150 mm

  • Steam Pressure — 16 bar(g)

  • Steam temperature (Ts) — 201oC

  • Enthalpy of evaporation corresponding to above parameters hfg — 1933

  • Ambient air temperature (Tamb) — 20oC

  • Length of the pipe shall be — 120 m

  • Cp of steel is —- 0.49 kj/kgo C

  • Warming-up time in minutes (t) — 30

  • Total weight of pipe plus flanges and fittings in kg (W)

  • Pipe network consists of 10 pairs of PN-40 flanged joints and two isolation valves

Table 1: Typical weights of steel pipe, flanges and bolts, and isolating valves in kg.

Pipe size(mm)

Sch.40 pipe kg/m

Flange weight per pair

Isolating valve flanged PN40





PN40

ANSI150

ANSI300


150

28.2

28.0

26.0

32

88

To find W, find the mass of the various steam main items from Table 1

  • 150 mm steel main = 28.2 kg/m

  • 150 mm flanges to PN-40 = 28 kg per pair

  • 150 mm stop valve = 88 kg each





Rate of condensation generated during warm-up time is given by:





Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Electrical4u

Electrical4U is dedicated to the teaching and sharing of all things related to electrical and electronics engineering.

Classification of Electric Power Distribution Network Systems
Classification of Electric Power Distribution Network Systems
The typical electric power system network is categorized into three main components: generation, transmission, and distribution. Electric power is produced in power plants, which are often located far from load centers. As a result, transmission lines are employed to deliver power over long distances.To minimize transmission losses, high-voltage power is used in transmission lines, and the voltage is reduced at the load center. The distribution system then delivers this power to end-users.Types
Edwiin
06/05/2025
Why is the Ground Wire Always Positioned Above the Overhead Power Lines?
Why is the Ground Wire Always Positioned Above the Overhead Power Lines?
Ground Wire in Overhead Transmission LinesThe ground wire (also called earth wire or OPGW) installed above phase lines in overhead transmission lines acts as a key protective and safety component. It provides lightning protection, ground fault defense, and helps prevent electrical system disruptions.In overhead transmission lines, positioning the ground wire above phase lines serves specific safety and performance purposes. Referred to as a "shield wire" or "static wire," this configuration has
Edwiin
06/04/2025
What is the Power Angle in a Power Transmission Line?
What is the Power Angle in a Power Transmission Line?
The power angle, denoted by δ, is the phase angle difference between two voltage levels in a power transmission line. Specifically, it represents the angular discrepancy between the sending-end voltage phasor and the receiving-end voltage (or between voltages at two bus points). In simpler terms, it quantifies the phase shift between voltage and current waveforms in the transmission line.Also referred to as the torque angle or load angle, this parameter is critical for two key reasons: it
Edwiin
06/04/2025
Permanent Magnet Moving Coil or PMMC Instrument
Permanent Magnet Moving Coil or PMMC Instrument
DefinitionInstruments that utilize a permanent magnet to generate a stationary magnetic field within which a coil moves are known as Permanent Magnet Moving Coil (PMMC) instruments. They operate on the principle that torque is exerted on a moving coil situated in the magnetic field of a permanent magnet. PMMC instruments provide accurate results for direct current (DC) measurements.Construction of PMMC InstrumentThe moving coil and the permanent magnet are the key components of a PMMC instrument
Edwiin
05/30/2025
Inquiry
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!